6.2 Setting Offsets (OFFST)

6.2Setting Offsets (OFFST)

When recording and showing data using the current input as the reference, measured values can be corrected within 10% of the span. For example, assume the reading is 1.998 V for the current level of input. If you want to change the reading to 2.000 V, set 0.002 V as the offset. This menu opens only when offset settings protection is turned on in the SET UP mode.

Key operation

ESC

DISP

3 sec

PRINT

CH UP

PRINT

 

CH UP

 

PRINT

FEED

CH UP

 

 

ESC

 

CH UP

DISP

3 sec

 

 

Indication

Discription

Enter the SET mode by pressing the [DISP] key for three

seconds. Using the [ ] key, show [] and then press the [ENT] key.

Using the [ ] key, select the channel to be configured and then press the [ENT] key. Configurable channels are those whose measuring range is VOLT, TC, RTD or SCL.

Type the value of offset. Use the [ ] key to move through the digits and the [ ] key to select a numeral. When setting is complete, press the [ENT] key. Note that set the offset within 10% of the recording span or scale.

[] is displayed and the setting is then completed. Press the [ENT] key to set another channel; or press the [DISP] key for three seconds to return to the OPERATION mode.

NOTE If you press the [ESC] key in the middle of setting, the indication returns to the

[] and already set data will be aborted.