Omega RD260A Alarm Output Wiring option, Contact characteristics, Output type, Output capacity

Models: RD260A

1 97
Download 97 pages 20.61 Kb
Page 20
Image 20

2.2.4 Alarm Output Wiring (option) !

NOTE The following settings are available only for the model with relay options (-A2, -A4, -A6).

(1)Turn the power switch off.

(2)Remove the transparent cover of the optional terminals.

(3)Connect the alarm output wires to the optional terminals.

(4)Cover the terminals with the transparent cover and secure the screws. Depending on the type (the number of outputs) of alarm relay options, the terminal arrangement changes as shown in the following:

 

ALARM

1

NO

C

NC

2

NO

C

NC

 

 

 

!

-A2 option

 

(2 outputs)

 

ALARM

1

NO

C

NC

2

NO

C

NC

3

NO

C

NC

4

NO

C

NC

 

 

 

!

- A4 option

(4 outputs)

 

ALARM

1

NO

C

NC

2

NO

C

NC

3

NO

C

NC

4

NO

C

NC

5

NO

C

NC

6

NO

C

NC

 

 

 

!

-A6 option

 

(6 outputs)

WARNING

NOTE

Alarm Output Terminal Arrangements

Contact characteristics:

Output type

: Relay transfer contacts

Output capacity

: 250

V AC (50/60 Hz), 3 A

 

250

V DC, 0.1 A (resistive load)

Dielectric strength

: 1500 V AC (50/60 Hz) for one minute between output terminals

 

and grounding terminals

To prevent an electric shock, ensure the main power switch is turned off before wiring.

To prevent an emission of electromagnetic disturbances, separate the alarm output wires from the power supply and input wires at least 0.1 m. Over 0.5 m is recommended.

2 - 8

Page 20
Image 20
Omega RD260A Alarm Output Wiring option, Contact characteristics, Output type, Output capacity, Dielectric strength