Issue 10/06

2 Electrical Installation

Input voltage range

 

 

3 AC 380 V – 480 V, ± 10 %

 

(Unfiltered)

Order No.

6SE6440-

2UD38-8FA1

2UD41-1FA1

2UD41-3GA1

2UD41-6GA1

2UD42-0GA1

Frame Size

 

 

 

FX

 

GX

 

Output Rating(CT)

 

[kW]

90

 

110

132

160

200

 

[hp]

125

 

150

200

250

300

 

 

 

Output Power

 

[kVA]

145,4

 

180

214,8

263,2

339,4

CT-Input Current 1)

 

[A]

169

 

200

245

297

354

CT-Output Current

 

[A]

178

 

205

250

302

370

VT-Input Current 1)

 

[A]

200

 

245

297

354

442

VT-Output Current

 

[A]

205

 

250

302

370

477

Recommended Fuse

 

[A]

250

 

315

400

450

560

 

3NE

1227-0

 

1230-0

1332-0

1333-0

1435-0

 

 

 

Pipe cable shoe to

 

[mm]

10

 

10

10

10

10

DIN 46235

 

 

 

 

 

 

 

 

 

 

 

 

[mm2]

1 x 95 or

 

1 x 150 or

1 x 185 or

1 x 240 or

2 x 95

Input Cable, min.

 

 

2 x 35

 

2 x 50

2 x 70

2 x 70

 

 

[AWG]

1 x 4/0 or

 

1 x 300 or

1 x 400 or

1 x 500 or

 

 

 

 

2 x 4/0

 

 

or

2 x 2

 

2 x 1/0

2 x 2/0

2 x 2/0

 

 

[kcmil]

 

 

 

 

 

 

 

 

 

 

 

 

[mm2]

1 x 185 or

 

1 x 185 or

2 x 240

2 x 240

2 x 240

Input Cable, max.

 

 

2 x 120

 

2 x 120

 

 

 

 

[AWG]

1 x 350 or

 

1 x 350 or

 

 

 

 

 

 

2 x 400

2 x 400

2 x 400

 

 

or

2 x 4/0

 

2 x 4/0

 

 

[kcmil]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[mm2]

1 x 95 or

 

1 x 150 or

1 x 185 or

1 x 240 or

2 x 95

Output Cable, min.

 

 

2 x 35

 

2 x 50

2 x 70

2 x 70

 

 

[AWG]

1 x 4/0 or

 

1 x 300 or

1 x 400 or

1 x 500 or

 

 

 

 

2 x 4/0

 

 

or

2 x 2

 

2 x 1/0

2 x 2/0

2 x 2/0

 

 

[kcmil]

 

 

 

 

 

 

 

 

 

 

 

 

[mm2]

1 x 185 or

 

1 x 185 or

2 x 240

2 x 240

2 x 240

Output Cable, max.

 

 

2 x 120

 

2 x 120

 

 

 

 

[AWG]

1 x 350 or

 

1 x 350 or

 

 

 

 

 

 

2 x 400

2 x 400

2 x 400

 

 

or

2 x 4/0

 

2 x 4/0

 

 

[kcmil]

 

 

 

 

 

 

 

 

 

 

 

 

Weight

 

[kg]

110

 

110

170

170

170

 

[lbs]

242

 

242

418

418

418

 

 

 

Tightening torques for

 

[Nm]

 

 

 

25

 

 

power terminals

 

[lbf.in]

 

 

 

(222,5)

 

 

1)Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line

supply Vk 2.33 % referred to the rated drive converter power and a rated line supply voltage of 400 V without line commutating reactor.

MICROMASTER 440

11

Operating Instructions (Compact)

Page 11
Image 11
Siemens 440 95 or 150 or 185 or 240 or, 4/0 or 300 or 400 or 500 or 1/0 2/0, 350 or 4/0, Recommended Fuse