6 Commissioning

Issue 10/06

P0335 = ...

P0601 = ...

A high thermal motor load and when the line supply is frequently switched- out/switched-in requires, for closed-loop vector control

that a KTY84 sensor is used, or

an external 24V power supply voltage is connected

Motor cooling (Selects motor cooling system used)

0

0Self-cooled: Using shaft mounted fan attached to motor

1Force-cooled: Using separately powered cooling fan

2Self-cooled and internal fan

3Force-cooled and internal fan

Motor temperature sensor

0

Selects the motor temperature sensor.

0No sensor

1PTC thermistor (PTC)

2KTY84

5 V

ADC

PTC

KTY

Fault

F0015

T1 = 4 s

Signal

loss

detection

Equivalent circuit data

Power dissipation

PV,mot

 

P0601 = 2

&

 

 

0

No sensor

 

PTC

 

1

 

KTY

 

2

 

 

 

 

ϑ

 

P0601

 

V

 

 

 

Thermal

r0631

 

motor

r0632

 

model

 

 

 

 

r0633

1

0

r0035

1

0

P0604

r0052

Bit13

Motor 1 temp. reaction

P0610

P0604 = ...

P0610 = ...

P0640 = ...

Alarm threshold, motor overtemperature

130.0 °C

Defines the alarm threshold for the motor overtemperature protection. This threshold, where either a shutdown (trip) or Imax reduction is initiated (P0610) always lies 10 % above the alarm threshold.

ϑtrip = 1.1ϑwarn = 1.1P0604

ϑwarn : Warning threshold (P0604)

 

ϑtrip : Trip threshold (max. permissible temperature)

The alarm threshold should be at least 40 °C greater than the ambient temperature P0625.

P0604 P0625 + 40 °C

Inverter temperature reaction

2

Defines reaction when motor temperature reaches warning threshold.

 

0

No reaction, warning only

 

1

Warning and Imax reduction (results in a lower output frequency)

 

2

Warning and trip (F0011)

 

Motor overload factor [%]

150.0 %

Defines motor overload current limit in [%] relative to p0305 (rated motor current). Limited to maximum inverter current or to 400 % of rated motor current (p0305), whichever is the lower.

46

MICROMASTER 440

Operating Instructions (Compact)

Page 46
Image 46
Siemens 440 Motor temperature sensor, Alarm threshold, motor overtemperature, Inverter temperature reaction