6 Commissioning

P1300 =...

P1500 =...

P1910 = ...

P1960 = ...

P3900 = 1

END

Control mode

0

(enters the required control mode)

0V/f with linear characteristic

1V/f with FCC

2V/f with parabolic characteristic

3V/f with programmable characteristic

5V/f for textile applications

6V/f with FCC for textile applications

19V/f control with independent voltage setpoint

20Sensorless Vector control

21Vector control with sensor

22Sensorless Vector torque-control

23Vector torque-control with sensor

Selection of torque setpoint *

0

(enters the source for the torque setpoint)

0No main setpoint

2Analog setpoint

4USS on BOP link

5USS on COM link (control terminals 29 and 30)

6CB on COM link (CB = communications module)

7Analog setpoint 2

Select motor data identification *

0

0

Disabled

 

 

 

Speed controller optimization *

0

0

Inhibited

 

In order to optimize the speed controller, the closed-loop vector control (P1300 = 20 or 21) must be activated. After the optimization has been selected

(P1960 = 1), Alarm A0542 is displayed.

End of quick commissioning

0

(start of the motor calculation)

 

0No quick commissioning (no motor calculations)

1Motor calculation and reset of all of the other parameters, which are not included in the quick commissioning (attribute "QC" = no), to the factory setting

2Motor calculation and reset of the I/O settings to the factory setting

3Only motor calculation. The other parameters are not reset.

NOTE

For P3900 = 1,2,3 P0340 is internally set to 1 and the appropriate data calculated.

End of the quick commissioning/drive setting

If additional functions must be implemented at the drive inverter, please use the Section "Commissioning the application" (refer to Section 6.4). We recommend this procedure for drives with a high dynamic response.

MICROMASTER 440

31

Operating Instructions (Compact)

Page 31