Issue 10/06 | 6 Commissioning |
P1300 =...
P1500 =...
P1910 = ...
P1960 = ...
P3900 = 1
END
Control mode | 0 |
(enters the required control mode)
0V/f with linear characteristic
1V/f with FCC
2V/f with parabolic characteristic
3V/f with programmable characteristic
5V/f for textile applications
6V/f with FCC for textile applications
19V/f control with independent voltage setpoint
20Sensorless Vector control
21Vector control with sensor
22Sensorless Vector
23Vector
Selection of torque setpoint * | 0 |
(enters the source for the torque setpoint)
0No main setpoint
2Analog setpoint
4USS on BOP link
5USS on COM link (control terminals 29 and 30)
6CB on COM link (CB = communications module)
7Analog setpoint 2
Select motor data identification * | 0 | |
0 | Disabled |
|
|
| |
Speed controller optimization * | 0 | |
0 | Inhibited |
|
In order to optimize the speed controller, the
(P1960 = 1), Alarm A0542 is displayed.
End of quick commissioning | 0 |
(start of the motor calculation) |
|
0No quick commissioning (no motor calculations)
1Motor calculation and reset of all of the other parameters, which are not included in the quick commissioning (attribute "QC" = no), to the factory setting
2Motor calculation and reset of the I/O settings to the factory setting
3Only motor calculation. The other parameters are not reset.
NOTE
For P3900 = 1,2,3 → P0340 is internally set to 1 and the appropriate data calculated.
End of the quick commissioning/drive setting
If additional functions must be implemented at the drive inverter, please use the Section "Commissioning the application" (refer to Section 6.4). We recommend this procedure for drives with a high dynamic response.
MICROMASTER 440 | 31 |
Operating Instructions (Compact) |