Issue 10/06

1 Installation

1 Installation

1.1Clearance distances for mounting

The inverters can be mounted adjacent to each other. When mounting inverters one above the other, the specified environmental conditions must not be exceeded.

Independent of this, these minimum distances must be observed.

¾Frame Size A, B, C above and below 100 mm

¾Frame Size D, E above and below 300 mm

¾Frame Size F above and below 350 mm

¾ Frame Size FX, GX above 250 mm below 150 mm

in front 40 mm (FX), 50 mm (GX)

1.2Mounting dimensions

 

 

Frame

Drilling Dimensions

Tightening Torque

 

 

Size

 

 

 

 

 

 

 

H

W

Bolts

Nm

 

 

 

mm (Inch)

mm (Inch)

 

(lbf.in)

 

 

 

 

 

 

 

 

 

A

160 (6.30)

2 x M4

2,5

 

 

 

 

 

 

 

 

B

174 (6.85)

138 (5.43)

4 x M4

 

 

(22.12)

 

 

 

 

 

 

 

 

C

204 (8.03)

174 (6.85)

4 x M5

 

H

 

 

 

 

 

 

 

D

486 (19.13)

235 (9.25)

4 x M8

 

 

 

 

 

 

 

 

 

 

E

616,4

235 (9.25)

4 x M8

3,0

 

 

 

(24.27)

 

 

W

 

 

 

 

 

(26.54)

 

F

810 (31.89)

300 (11.81)

4 x M8

 

 

 

 

 

 

 

 

 

 

 

FX

1375,5

250 (9.84)

6 x M8

13,0

 

 

 

(54.14)

 

 

 

 

 

 

 

(115.02)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GX

1508,5

250 (9.84)

6 x M8

13,0

 

 

 

(59.38)

 

 

 

 

 

 

 

(115.02)

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 1-1

Mounting dimensions

 

 

 

MICROMASTER 440

5

Operating Instructions (Compact)

Page 5