6 Commissioning

6.5Series commissioning

An existing parameter set can be transferred to a MICROMASTER 440 frequency inverter using STARTER or DriveMonitor (refer to Section 4.1 "Establishing communications MICROMASTER 440 STARTER").

Typical applications for series commissioning include:

1.If several drives are to be commissioned that have the same configuration and same functions. A quick / application commissioning (first commissioning) must be carried-out for the first drive. Its parameter values are then transferred to the other drives.

2.When replacing MICROMASTER 440 frequency inverters.

6.6Parameter reset of factory setting

START

P0003 = 1

P0004 = 0

P0010 = 30

P0970 = 1

END

User access level

1

1

Standard

 

 

 

Parameter filter

0

0

All parameters

 

 

 

Commissioning parameter

0

30

Factory setting

 

 

 

Factory reset

0

0disabled

1Parameter reset

The drive inverter carries-out a parameter reset (duration, approx. 10 s) and then automatically exits the reset menu and sets:

P0970 = 0 : disabled

P0010 = 0 : ready