Issue 10/06 | 6 Commissioning |
6.4.18Converter-specific Functions
6.4.18.1Flying start
P1200 = ...
P1202 = ...
P1203 = ?
Flying start | 0 |
Starts inverter onto a spinning motor by rapidly changing the output frequency of the inverter until the actual motor speed has been found.
0Flying start disabled
1Flying start is always active, start in direction of setpoint
2Flying start is active if power on, fault, OFF2, start in direction of setpoint
3Flying start is active if fault, OFF2, start in direction of setpoint
4Flying start is always active, only in direction of setpoint
5Flying start is active if power on, fault, OFF2, only in direction of setpoint
6Flying start is active if fault, OFF2, only in direction of setpoint
100 % | |
Defines search current used for flying start. |
|
|
|
Search rate: Flying start (entered in %) | 100 % |
Sets factor by which the output frequency changes during flying start to synchronize with turning motor.
6.4.18.2Automatic restart
P1210 = ... Automatic restart
Configures automatic restart function.
0Disabled
1Trip reset after power on
2Restart after mains blackout
3Restart after mains brownout or fault
4Restart after mains brownout
5Restart after mains blackout and fault
6Restart after mains brown/blackout or fault
1
MICROMASTER 440 | 55 |
Operating Instructions (Compact) |