Issue 10/06

6 Commissioning

Example:

1.Commissioning steps with a motor:

Carry-out commissioning at DDS1.

Connect P0820 (P0821 if required) to the DDS changeover source (e.g. using DIN 4: P0704[0] = 99, P0820 = 722.3).

Copy DDS1 to DDS2 (P0819[0] = 0, P0819[1] = 1, P0819[2] = 2).

Adapt DDS2 parameters

(e.g. ramp-up / ramp-down times P1120[1] and P1121[1]).

DIN

 

 

Sequence control

 

 

 

 

 

 

 

 

 

Gating unit

M

ADC

DIN4

SUM

setpoint

P0820 = 722.3

AFM

 

RFG

 

Motor

 

 

control

 

 

 

 

0

1

P1120

P1121

[0] [1] [2]

DDS1 DDS2 DDS3

2.Commissioning steps with 2 motors (motor 1, motor 2):

Commission motor 1; adapt the remaining DDS1 parameters.

Connect P0820 (P0821 if required) to the DDS changeover source (e.g. via DIN 4: P0704[0] = 99, P0820 = 722.3).

Changeover to DDS2 (check using r0051).

Commission motor 2; adapt the remaining DDS2 parameters.

 

M1

Motor 1

MM4

K1

 

 

M2

Motor 2

 

K2

 

MICROMASTER 440

71

Operating Instructions (Compact)

Page 71