Issue 10/06

2 Electrical Installation

Input voltage range

3 AC 200 V – 240 V. ± 10 %

(with built in Class A Filter)

 

 

 

Order No.

6SE6440-

2AC23-

2AC24-

2AC25-

 

 

0CA1

0CA1

5CA1

Frame Size

 

 

C

 

Output Rating(CT)

[kW]

3,0

4,0

5,5

[hp]

4,0

5,0

7,5

 

Output Power

[kVA]

6,0

7,7

9,6

CT Input Current 1)

[A]

15,6

19,7

26,5

CT-Output Current

[A]

13,6

17,5

22,0

VT Input Current 1)

[A]

-

28,3

34,2

VT-Output Current

[A]

-

22,0

28,0

Fuse

[A]

25

32

35

Recommended

3NA

3810

3812

3814

For UL specified

 

*

*

*

Input Cable, min.

[mm2]

2,5

4,0

4,0

[AWG]

14

12

12

 

Input Cable, max.

[mm2]

10,0

10,0

10,0

[AWG]

8

8

8

 

Output Cable, min.

[mm2]

1,5

4,0

4,0

[AWG]

16

12

12

 

Output Cable, max.

[mm2]

10,0

10,0

10,0

[AWG]

8

8

8

 

Weight

[kg]

5,7

5,7

5,7

[lbs]

12,5

12,5

12,5

 

Tightening torques for

[Nm]

 

2,25

 

power terminals

[lbf.in]

 

(20)

 

1)Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 240 V without line commutating reactor.

*UL listed fuses such as Class NON from Bussmann are required for use in America

MICROMASTER 440

7

Operating Instructions (Compact)

Page 7
Image 7
Siemens Order No 6SE6440, 26,5, CT-Output Current 13,6, 22,0, VT Input Current, 34,2, VT-Output Current, 28,0