2 Electrical Installation

Issue 10/06

2 Electrical Installation

2.1Technical Specifications

Input voltage range

 

1 AC 200 V – 240 V, ± 10 %

 

 

 

 

 

(Unfiltered and with built in Class A Filter)

 

 

 

 

 

 

Order No

2AB

11-

12-

13-

15-

17-

21-

21-

22-

23-

6SE6440-

2UC

2AA1

5AA1

7AA1

5AA1

5AA1

1BA1

5BA1

2BA1

0CA1

Frame Size

 

 

 

A

 

 

 

B

 

C

Output Rating (CT)

[kW]

0,12

0,25

0,37

0,55

0,75

1,1

1,5

2,2

3,0

[hp]

0,16

0,33

0,5

0,75

1,0

1,5

2,0

3,0

4,0

 

Output Power

[kVA]

0,4

0,7

1,0

1,3

1,7

2,4

3,2

4,6

6,0

CT Input Current 1)

 

1,8

3,2

4,6

6,2

8,2

11,0

14,4

20,2

35,5

CT Output Current

[A]

0,9

1,7

2,3

3,0

3,9

5,5

7,4

10,4

13,6

Fuse

 

10

10

10

16

16

20

20

32

40

Recommended

3NA

3803

3803

3803

3805

3805

3807

3807

3812

3817

for UL specified

 

*

*

*

*

*

*

*

*

*

Input Cable Min.

[mm2]

1,0

1,0

1,0

1,5

1,5

2,5

2,5

4,0

6,0

[AWG]

18

18

18

16

16

14

14

12

10

 

Input Cable Max.

[mm2]

2,5

2,5

2,5

2,5

2,5

6,0

6,0

6,0

10,0

[AWG]

14

14

14

14

14

10

10

10

8

 

Output Cable Min.

[mm2]

1,0

1,0

1,0

1,0

1,0

1,0

1,0

1,0

1,5

[AWG]

18

18

18

18

18

18

18

18

16

 

Output Cable Max.

[mm2]

2,5

2,5

2,5

2,5

2,5

6,0

6,0

6,0

10,0

[AWG]

14

14

14

14

14

10

10

10

8

 

Weight

[kg]

1,3

1,3

1,3

1,3

1,3

3,4

3,4

3,4

5,7

(with built in filter)

[lbs]

2,9

2,9

2,9

2,9

2,9

7,5

7,5

7,5

12,5

Weight (unfiltered)

[kg]

1,3

1,3

1,3

1,3

1,3

3,3

3,3

3,3

5,5

[lbs]

2,9

2,9

2,9

2,9

2,9

7,3

7,3

7,3

12,1

 

Tightening torques for

[Nm]

 

 

1,1

 

 

 

1,5

 

2,25

power terminals

[lbf.in]

 

 

(10)

 

 

 

(13,3)

 

(20)

1)Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 240 V without line commutating reactor.

*UL listed fuses such as Class NON from Bussmann are required for use in America

6

MICROMASTER 440

Operating Instructions (Compact)

Page 6
Image 6
Siemens 440 operating instructions Technical Specifications, Input voltage range