Issue 10/06

6 Commissioning

6.4.9

P1001 = ...

P1002 = ...

P1003 = ...

P1004 = ...

P1005 = ...

P1006 = ...

P1007 = ...

P1008 = ...

P1009 = ...

P1010 = ...

P1011 = ...

P1012 = ...

P1013 = ...

P1014 = ...

P1015 = ...

P1016 = ...

P1017 = ...

P1018 = ...

P1019 = ...

P1025 = ...

P1027 = ...

Fixed frequency (FF)

Fixed frequency 1

0.00 Hz

 

 

Can be directly selected via DIN1

 

 

 

(P0701 = 15, 16)

 

 

 

 

 

 

 

 

Fixed frequency 2

5.00 Hz

 

 

Can be directly selected via DIN2

 

 

 

(P0702 = 15, 16)

 

 

 

 

 

 

 

 

 

Fixed frequency 3

10.00

Hz

 

 

Can be directly selected via DIN3

 

 

 

(P0703 = 15, 16)

 

 

When defining the function of the digital inputs

 

 

 

Fixed frequency 4

15.00

Hz

(P0701 to P0703), three different types can be

Can be directly selected via DIN4

 

selected for fixed frequencies:

(P0704 = 15, 16)

 

 

15 = Direct selection (binary-coded)

 

 

 

 

In this particular mode, the appropriate

Fixed frequency 5

20.00

Hz

 

 

digital input always selects the associated

 

 

 

Can be directly selected via DIN5

 

 

fixed frequency, e.g.:

(P0705 = 15, 16)

 

 

 

Digital input 3 = selects fixed frequency 3.

 

 

 

 

If several inputs are simultaneously active,

Fixed frequency 6

25.00

Hz

 

 

then these are summed. An ON command is

Can be directly selected via DIN6

 

 

 

 

additionally required.

(P0706 = 15, 16)

 

 

16 = Direct selection + ON command

 

 

 

 

(binary-coded + On / Off1)

Fixed frequency 7

30.00

Hz

 

 

In this mode, the fixed frequencies are

 

 

 

 

 

 

 

 

selected as for 15, however these are

Fixed frequency 8

35.00

Hz

 

 

combined with an ON command.

 

 

 

 

 

 

17 = Binary coded selection + ON command

Fixed frequency 9

40.00

Hz

 

(BCD-coded + On/ Off1)

 

 

 

 

 

 

The BCD-coded operating mode is effective for

Fixed frequency 10

45.00

Hz

digital inputs 1 to 3.

 

 

 

 

 

Fixed frequency 11

50.00

Hz

 

 

 

 

 

 

 

Fixed frequency 12

55.00

Hz

 

 

 

 

 

 

 

Fixed frequency 13

60.00

Hz

 

 

 

 

 

 

 

Fixed frequency 14

65.00

Hz

 

 

 

 

 

 

 

Fixed frequency 15

65.00

Hz

 

 

 

 

 

 

 

Fixed frequency code - Bit 0

1

 

1

Direct selection

Defines the selection method for fixed

2

Direct selection + ON command

frequencies.

 

 

3 Binary coded selection + ON command

 

 

 

NOTE

Fixed frequency code - Bit 1

1

 

 

For settings 2 and 3, all parameters P1016 to

 

 

 

 

 

 

P1019 must be set to the selected value so that

Fixed frequency code - Bit 2

1

 

 

the drive inverter accepts the ON command.

 

 

 

 

 

 

 

 

Fixed frequency code - Bit 3

1

 

 

 

 

 

 

 

 

Fixed frequency code - Bit 4

1

 

1

Direct selection

 

 

 

2 Direct selection + ON command

Fixed frequency code - Bit 5

1

 

 

 

 

 

 

 

 

MICROMASTER 440