Issue 10/06

2 Electrical Installation

Input voltage range

 

3 AC 380 V – 480 V. ± 10 %

 

 

 

 

 

 

 

 

(with built in Class A Filter)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Order No.

6SE6440-

2AD22-

 

 

2AD23-

2AD24-

 

2AD25-

2AD27-

 

2AD31-

 

2AD31-

 

 

 

2BA1

 

 

0BA1

 

0BA1

 

 

5CA1

5CA1

 

1CA1

 

5DA1

Frame Size

 

 

 

 

 

B

 

 

 

 

 

C

 

 

 

D

Output Rating(CT)

 

[kW]

2,2

 

3,0

 

4,0

 

5,5

7,5

11,0

15,0

 

[hp]

3,0

 

4,0

 

5,0

 

7,5

10,0

15,0

20,0

 

 

 

 

 

Output Power

 

[kVA]

4,5

 

5,9

 

7,8

 

10,1

14,0

19,8

24,4

CT-Input Current 1)

 

[A]

7,5

 

10,0

 

12,8

 

15,6

22,0

23,1

33,8

CT-Output Current

 

[A]

5,9

 

7,7

 

10,2

 

13,2

18,4

26,0

32,0

VT-Input Current 1)

 

[A]

 

 

 

 

17,3

23,1

33,8

37,0

VT-Output Current

 

[A]

 

 

 

 

20,2

29,0

39,0

45,2

Fuse

 

[A]

16

 

16

 

20

 

20

32

35

50

Recommended

 

3NA

3805

 

3805

 

3807

 

3807

3812

3814

3820

For UL specified

 

3NE

*

 

*

 

*

 

*

*

*

1817-0

Input Cable, min.

 

[mm2]

1,5

 

1,5

 

2,5

 

2,5

4,0

6,0

10,0

 

[AWG]

16

 

16

 

14

 

14

12

10

8

 

 

 

 

 

Input Cable, max.

 

[mm2]

6,0

 

6,0

 

6,0

 

10,0

10,0

10,0

35,0

 

[AWG]

10

 

10

 

10

 

8

8

8

2

 

 

 

 

 

Output Cable, min.

 

[mm2]

1,0

 

1,0

 

1,0

 

2,5

4,0

6,0

10,0

 

[AWG]

18

 

18

 

18

 

14

12

10

8

 

 

 

 

 

Output Cable, max.

 

[mm2]

6,0

 

6,0

 

6,0

 

10,0

10,0

10,0

35,0

 

[AWG]

10

 

10

 

10

 

8

8

8

2

 

 

 

 

 

Weight

 

[kg]

3,4

 

3,4

 

3,4

 

5,7

5,7

5,7

17,0

 

[lbs]

7,5

 

7,5

 

7,5

 

12,5

12,5

12,5

37,0

 

 

 

 

 

Tightening torques for

 

[Nm]

 

1,1

 

 

 

 

 

1,5

 

 

2,25

power terminals

 

[lbf.in]

 

(10)

 

 

 

 

 

(13,3)

 

 

(20)

 

 

 

 

 

 

 

 

 

 

 

Order No.

6SE6440-

2AD31-

 

 

2AD32-

2AD33-

2AD33-

2AD34-

2AD35-

2AD37-

 

 

 

8DA1

 

 

2DA1

 

0EA1

 

 

7EA1

5FA1

 

5FA1

 

5FA1

Frame Size

 

 

 

D

 

 

E

 

 

F

 

 

Output Rating(CT)

 

[kW]

18,5

 

22,0

 

30,0

 

37,0

45,0

 

55,0

 

75,0

 

[hp]

25,0

 

 

30,0

 

40,0

 

 

50,0

60,0

 

75,0

 

100,0

 

 

 

 

 

 

 

Output Power

 

[kVA]

29,0

 

34,3

 

47,3

 

57,2

68,6

 

83,8

 

110,5

CT-Input Current 1)

 

[A]

37,0

 

43,0

 

59,0

 

72,0

87,0

 

104,0

 

139,0

CT-Output Current

 

[A]

38,0

 

45,0

 

62,0

 

75,0

90,0

 

110,0

 

145,0

VT-Input Current 1)

 

[A]

43,0

 

59,0

 

72,0

 

87,0

104,0

 

139,0

 

169,0

VT-Output Current

 

[A]

45,0

 

62,0

 

75,0

 

90,0

110,0

 

145,0

 

178,0

Fuse

 

[A]

63

 

80

 

100

 

125

160

 

200

 

250

Recommended

 

3NA

3822

 

3824

 

3830

 

3832

3836

 

3140

 

3144

For UL specified

 

3NE

1818-0

 

1820-0

 

1021-0

 

1022-0

1224-0

 

1225-0

 

1227-0

Input Cable, min.

 

[mm2]

10,0

 

16,0

 

25,0

 

25,0

35,0

 

70,0

 

95,0

 

[AWG]

8

 

 

6

 

3

 

 

3

2

 

2/0

 

3/0

 

 

 

 

 

 

 

Input Cable, max.

 

[mm2]

35,0

 

35,0

 

35,0

 

35,0

150,0

 

150,0

 

150,0

 

[AWG]

2

 

 

2

 

2

 

 

2

300

 

300

 

300

 

 

 

 

 

 

 

Output Cable, min.

 

[mm2]

10,0

 

16,0

 

25,0

 

25,0

50,0

 

70,0

 

95,0

 

[AWG]

8

 

 

6

 

3

 

 

3

1/0

 

2/0

 

3/0

 

 

 

 

 

 

 

Output Cable, max.

 

[mm2]

35,0

 

35,0

 

35,0

 

35,0

150,0

 

150,0

 

150,0

 

[AWG]

2

 

 

2

 

2

 

 

2

300

 

300

 

300

 

 

 

 

 

 

 

Weight

 

[kg]

17,0

 

17,0

 

22,0

 

22,0

75,0

 

75,0

 

75,0

 

[lbs]

37,0

 

 

37,0

 

48,0

 

 

48,0

165,0

 

165,0

 

165,0

 

 

 

 

 

 

 

Tightening torques for

 

[Nm]

 

 

 

 

10

 

 

 

 

50

 

 

power terminals

 

[lbf.in]

 

 

 

 

(89)

 

 

 

 

(445)

 

 

1)Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 400 V without line commutating reactor.

*UL listed fuses such as Class NON from Bussmann are required for use in America

MICROMASTER 440

9

Operating Instructions (Compact)

Page 9
Image 9
Siemens 440 2AD23 2AD24, 2AD27, 2AD31, 2BA1 0BA1, Frame Size Output RatingCT, Power terminals Lbf.in, 2AD34, 2AD37