6 Commissioning | Issue 10/06 |
6.4Commissioning the application
An application is commissioned to adapt/optimize the frequency inverter - motor combination to the particular application. The frequency inverter offers numerous functions - but not all of these are required for the particular application. These functions can be skipped when commissioning the application. A large proportion of the possible functions are described here; refer to the parameter list for additional functions.
Parameters, designated with a * offer more setting possibilities than are actually listed here. Refer to the parameter list for additional setting possibilities.
START
P0003 = 3
User access level *
1Standard: Allows access into most frequently used parameters
2Extended: Allows extended access e.g. to inverter I/O functions
3Expert (For expert use only)
1
6.4.1Serial Interface (USS)
P2010 =...
P2011 =...
P2012 =...
P2013 =...
USS baud rate | 6 | Possible | ||
Sets baud rate for USS communication. |
| Settings: | ||
|
| 4 | 2400 Baud | |
|
| 5 | 4800 Baud | |
USS address | 0 | |||
6 | 9600 Baud | |||
Sets unique address for inverter. |
| 7 | 19200 Baud | |
|
| 8 | 38400 Baud | |
USS PZD length | 2 | |||
Defines the number of | 9 | 57600 Baud | ||
10 | 76800 Baud | |||
|
| |||
USS PKW length | 127 | 11 | 93750 Baud | |
Defines the number of | 12 | 115200 Baud | ||
|
|
|
|
6.4.2Selection of command source
P0700 =...
Selection of | 2 |
command source
Selects digital command source.
0Factory fault setting
1BOP (keypad)
2Terminal
4USS on BOP link
5USS on COM link
6CB on COM link
BOP |
|
|
|
|
|
Terminals |
|
| P0700 = 2 |
| |
USS | |
BOP link |
|
|
|
USS |
|
COM link |
|
|
|
CB |
|
COM link |
|
Sequence control
Setpoint |
|
| Motor |
channel |
|
| control |
|
| ||
|
|
|
|
34 | MICROMASTER 440 |
Operating Instructions (Compact) |