6 Commissioning

Issue 10/06

6 Commissioning

6.1Quick commissioning

The frequency inverter is adapted to the motor using the quick commissioning function and important technological parameters are set. The quick commissioning shouldn't be carried-out if the rated motor data saved in the frequency inverter (4-pole 1LA Siemens motor, star circuit configuration frequency inverter (FU)- specific) match the rating plate data.

Parameters, designated with a * offer more setting possibilities than are actually listed here. Refer to the parameter list for additional setting possibilities.

START

Factory setting

 

 

User access level *

1

P0003 = 3

 

 

1

Standard: Allows access into most frequently used parameters

 

 

 

 

2

Extended: Allows extended access e.g. to inverter I/O functions

 

 

3

Expert (For expert use only)

 

 

 

 

 

 

 

Parameter filter *

0

P0004 = 0

 

0All parameters

2Inverter

3Motor

4Speed sensor

 

 

Commissioning parameter *

0

P0010 = 1

 

 

0

Ready

 

 

 

 

1

Quick commissioning

 

 

30

Factory setting

 

 

 

 

NOTE

 

 

 

 

 

 

 

P0010 should be set to 1 in order to parameterize the data of the motor rating

 

 

 

plate.

 

 

 

 

P0100 =...

Europe/ North America

 

0

(enters the line supply frequency)

 

 

 

 

 

2

 

P0100= 0

0

Europe [kW], frequency default 50 Hz

 

P0100= 1,

 

1

North America [hp], frequency default 60 Hz

 

 

2

North America [kW], frequency default 60 Hz

 

 

For P0100 = 0 or 1, the setting of switch DIP50/60 determines the value of

 

 

 

 

NOTE

 

 

 

 

 

 

 

P0100.

 

 

 

 

 

 

 

 

OFF

=

kW, 50 Hz

 

 

 

 

 

ON

=

hp, 60 Hz

 

 

 

 

 

 

 

 

 

P0205 =...

Inverter application (enters the required torque)

 

0

P0205 =...

 

 

 

 

 

 

 

0

Constant torque (e.g. compressors, processing machines)

 

 

 

 

 

 

 

 

1

Variable torque (e.g. pumps, fans)

 

 

 

 

NOTE

 

 

 

 

 

 

 

This parameter is only effective for drive inverters 5.5 kW / 400 V

 

 

 

 

 

 

 

 

 

P0300 =...

Select motor type

 

1

P0300 =...

 

 

 

 

1Asynchronous motor (induction motor)

2Synchronous motor

NOTE

For P0300 = 2 (synchronous motor), only the V/f control types (P1300 < 20) are permitted.

28

MICROMASTER 440

Operating Instructions (Compact)