6 Commissioning

6.4.11Ramp function generator (RFG)

P1091 = ...

P1092 = ...

P1093 = ...

P1094 = ...

P1101 = ...

P1120 = ...

P1121 = ...

P1130 = ...

P1131 = ...

P1132 = ...

P1133 = ...

P1134 = ...

P1135 = ...

Skip frequency 1 (entered in Hz)

0.00 Hz

fout

Defines skip frequency 1, which avoids

effects of mechanical resonance and

 

 

 

suppresses frequencies within +/- p1101

 

 

 

(skip frequency bandwidth).

 

 

 

Skip frequency 2

0.00 Hz

 

 

 

 

 

 

Skip frequency 3

0.00 Hz

 

 

 

p1101

 

 

 

 

 

 

 

 

 

Skip frequency 4

0.00 Hz

 

 

 

Skip frequency

 

 

 

 

 

bandwidth

 

 

 

 

 

 

p1091

fin

 

 

Skip frequency bandwidth

2.00 Hz

 

 

 

 

 

 

 

Skip frequency

 

 

(entered in Hz)

 

 

 

 

 

 

 

Ramp-up time

10.00 s

 

 

f

 

 

 

(enters the accelerating time in s)

 

p1082

 

 

 

 

 

 

(fmax)

 

 

 

 

 

 

 

f1

 

 

 

 

Ramp-down time

10.00 s

 

 

 

 

 

 

(enters the deceleration time in s)

 

 

 

 

 

 

 

 

 

 

 

p1120

p1121

 

t

 

 

 

 

 

 

Rump-up initial rounding time

0.00 s

 

f

 

 

 

 

(entered in s)

 

f2

 

 

 

 

 

 

0.00 s

 

 

 

 

 

Ramp-up final rounding time

 

 

 

 

 

 

(entered in s)

 

 

 

 

 

 

 

Rump-down initial rounding time

0.00 s

 

 

 

 

 

 

(entered in s)

 

 

 

 

 

 

 

Ramp-down final rounding time

0.00 s

f1

 

 

 

 

 

(entered in s)

 

P1130

P1131

P1132

P1133

t

 

 

Rounding type

0

 

 

tup

tdown

 

 

 

 

 

 

 

 

0

Continuous smoothing

The rounding times are recommended as

1

Discontinuous smoothing

abrupt responses can be avoided therefore

 

 

reducing stress and damage to the mechanical

 

 

system.

 

 

The ramp-up and ramp-down times are

 

 

extended by the component of the rounding

 

 

ramps.

OFF3 ramp-down time

 

5.00 s

Defines ramp-down time from maximum frequency to standstill for OFF3 command.