6 Commissioning

P1312 =...

P1320 =...

P1321 =...

P1322 =...

P1323 =...

P1324 =...

P1325 =...

P1333 = ...

P1335 = ...

P1338 =...

Starting boost (entered in %)

0.0 %

Voltage boost when starting (after an ON command) when using the linear or square-law V/f characteristic as a % relative to P0305 (rated motor current) or P0350 (stator resistance). The voltage boost remains active until

1)the setpoint is reached for the first time and

2)the setpoint is reduced to a value that is less than the instantaneous ramp-function generator output.

Programmable V/f freq.

0.0 Hz

V

 

 

 

 

 

 

 

 

 

coord. 1

 

V

 

Vmax = f(Vdc, Mmax)

 

 

 

 

 

Sets V/f coordinates

 

max

 

 

 

 

 

 

 

 

 

(P1320/1321 to P1324/1325) to

r0071

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

define V/f characteristic.

 

Vn

 

 

 

 

 

 

 

 

 

Programmable. V/f volt. 0.0 Hz

P0304

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

coord. 1

 

P1325

 

 

 

 

 

 

 

 

 

Programmable V/f freq. 0.0 Hz

 

 

 

 

 

 

 

 

 

P1323

 

 

 

 

 

 

 

 

 

coord. 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Programmable V/f volt.

0.0 Hz

P1321

 

 

 

 

 

 

 

 

 

coord. 2

 

P1310

 

 

 

 

 

 

 

 

 

Programmable U/f Freq. 0.0 Hz

 

 

 

 

 

 

 

 

 

 

coord. 3

 

f0

 

f1

f2

 

 

f3

fn

fmax

f

Programmable V/f volt.

0.0 Hz

 

 

 

0 Hz

P1320

P1322

P1324

P0310

P1082

 

coord. 3

 

 

 

P1310[%]

r0395[%]

 

 

 

 

 

 

P1310[V] =

P0304[V]

 

 

 

 

 

 

100[%]

100[%]

 

 

 

 

Starting frequency for FCC

10.0 %

 

 

 

 

 

 

 

 

 

(entered as a %)

 

over-Switch

FCC

 

 

Defines the FCC starting frequency as a

 

V/f

 

 

 

 

 

 

 

 

 

function of the rated motor frequency (P0310).

 

 

 

 

 

 

 

 

 

 

 

 

fFCC = P0310P1333

 

 

 

 

 

 

 

100

 

 

 

 

 

 

 

 

fFCC+Hys = P0310(P1333 + 6%)

 

 

 

 

 

 

 

100

 

 

 

 

 

 

 

f

 

 

 

 

 

 

NOTE

 

 

 

 

fFCC

fFCC+Hys

 

 

 

 

 

 

The constant voltage boost P1310 is

 

 

 

 

 

 

 

continually decreased analog to switching-in

 

 

 

 

 

 

FCC.

 

 

 

 

 

 

 

Slip compensation

 

0.0 %

Range of slip compensation :

 

 

(entered in %)

%

 

 

Dynamically adjusts output frequency of

 

 

 

inverter so that motor speed is kept constant

P1335

 

 

independent of motor load.

 

 

 

 

 

 

f out

 

6 % 10 %

100 %

fN

Resonance damping gain V/f

 

 

0.00

Defines resonance damping gain for V/f.

MICROMASTER 440

49

Operating Instructions (Compact)