Issue 10/06

6 Commissioning

6.4.7

P0771 = ...

P0773 =...

P0775 = ...

P0776 = ...

P0777 = ...

P0778 = ...

P0779 = ...

P0780 = ...

P0781 = ...

Analog output (DAC)

CI: DAC

21

Defines function of the 0 - 20 mA analog output.

21 CO: Output frequency (scaled according to P2000)

24CO: Frequency inverter output frequency (scaled according to P2000)

25CO: Output voltage (scaled according to P2001)

26CO: DC link voltage (scaled according to P2001)

27CO: Output current (scaled according to P2002)

NOTE

For P0771 to P0781, the following applies:

Index 0 : Analog output 1 (DAC1), terminals 12, 13

Index 1 : Analog output 2 (DAC2), terminals 26, 27

Smooth time DAC

2 ms

Defines smoothing time [ms] for analog output signal. This parameter enables smoothing for DAC using a PT1 filter.

Permit absolute value

Decides if the absolute value of the analog output is used. If enabled, this parameter will take the absolute value of the value to be outputed. If the value was originally negative then the corresponding bit in r0785 is set, otherwise it is cleared.

0OFF

1ON

DAC type

0

Defines the analog output type.

0Current output

1Voltage output

NOTE

P0776 changes the scaling of r0774 (0 – 20 mA 0 – 10 V)

Scaling parameters P0778, P0780 and the dead zone are always entered in 0 – 20 mA For the DAC as voltage output, the DAC outputs must be terminated using a 500 resistor

Value x1 of DAC scaling

0.0 %

 

Defines the output characteristic value

mA

 

 

 

x1 as a %.

 

 

 

 

 

This parameter represents the lowest

20

 

 

 

analog value as a % of P200x

 

 

 

 

 

 

 

 

 

(depending on the setting of P0771).

P0780

 

 

 

 

 

 

 

 

Value y1 of DAC scaling

0

y2

 

 

 

P0781

 

 

 

This parameter represents the value for

 

 

 

x1 in mA.

 

P0778

 

 

 

 

100.0 %

y1

 

 

 

Value x2 of DAC scaling

 

 

 

 

Defines the output characteristic value

 

 

 

 

x2 as a %.

 

 

 

100 %

%

This parameter represents the lowest

P0777

P0779

analog value as a % of P200x

 

x1

x2

 

 

(depending on the setting of P0771).

 

 

 

 

Value y2 of DAC scaling

 

 

 

20

This parameter represents the value for x2 in mA.

 

 

 

Width of DAC deadband

 

 

 

 

0

Sets width of deadband in [mA] for analog output.