Parameters

 

Setpoints

 

Action

When

 

ON

OFF Status Alarm

Relay

 

 

 

Level H or HH

85%

70%

On

On

de-energizes

Level rises to 85%

 

 

 

Off

Off

energizes

Level falls to 70%

 

 

 

 

 

 

 

Level L or LL

15%

30%

On

On

de-energizes

Level falls to 15%

 

 

 

Off

Off

energizes

Level rises to 30%

In bounds !

80%

50%

On

On

de-energizes

Level falls to 78%

 

 

 

Off

Off

energizes

Level rises to 82%

 

 

 

On

On

de-energizes

Level rises to 52%

 

 

 

Off

Off

energizes

Level falls to 48%

 

 

 

 

 

 

 

Out of bounds

80%

50%

Off

Off

energizes

Level falls to 78%

!

 

 

 

 

 

 

 

 

 

On

On

de-energizes

Level rises to 82%

 

 

 

Off

Off

energizes

Level rises to 52%

 

 

 

On

On

de-energizes

Level falls to 48%

Rate of change

+10%

+5%

Off

Off

de-energizes

Fill rate increases to 10%/min

 

 

 

On

On

energizes

Fill rate decreases to 5%/min

 

-10%

-5%

Off

Off

de-energizes

Empty rate increases to 10%/min

 

 

 

On

On

energizes

Empty rate decreases to 5%/min

 

 

 

 

 

 

Temperature rises to 60°C

Temperature

60

55

On

On

de-energizes

 

 

 

Off

Off

energizes

Temperature falls to 55°C

 

-30

-25

On

On

de-energizes

Temperature falls to -30°C

 

 

 

Off

Off

energizes

Temperature rises to -25°C

Pump

80%

20%

On

On

energizes

Start pump down on level at 80%

 

 

 

Off

Off

de-energizes

Stop pump down on level at 20%

 

20%

80%

On

On

energizes

Start pump up on level at 20%

 

 

 

 

 

 

 

 

 

 

Off

Off

de-energizes

Stop pump up on level at 80%

 

 

 

 

 

 

 

*Values shown are for illustration purposes only. Enter values which apply to your particular installation.

!2% factory set deadband, adjustable via P116

Page 44