Siemens LU01 instruction manual P112 Relay on Setpoint, P113 Relay OFF Setpoint, P116 Dead Band

Models: LU01

1 114
Download 114 pages 47.65 Kb
Page 51
Image 51

P112 Relay ON Setpoint

Sets the process point at which the relay changes from its NORMAL state.

Primary Index

Relay

Values

Range: -999 to 9999

 

 

Preset: ----

 

Altered by

P007 Span

 

P100 Preset Applications

Related

P111 Relay Control Function

 

P113 Relay OFF Setpoint

 

 

 

For most applications, the relay is tripped at this point. For IN-BOUNDS and OUT-OF- BOUNDS alarms, it is the high point in the specified range. This parameter is set according to Span (P007) even when another reading, such as volume, is shown on the LCD.

Note: Relay ON and Relay OFF setpoint values cannot be exactly equal.

P113 Relay OFF Setpoint

Sets the process point at which the relay returns to its NORMAL state.

Primary Index

Relay

Values

Range: -999 to 9999

 

 

Preset: ----

 

Altered by

P007 Span

 

P100 Preset Applications

Related

P111 Relay Control Function

 

P112 Relay ON Setpoint

 

 

 

For most applications, the relay is reset at this point. For IN-BOUNDS and OUT-OF- BOUNDS alarms, it is the low point in the specified range. This parameter is set according to Span (P007), even when another reading, such as volume, is shown on the LCD.

P116 Dead Band

The distance above and below the bound alarm setpoints.

Primary Index

Relay

 

Values

Range: 0.000 to 9999

 

 

 

Preset: 2% of span

 

 

P111 Relay Control Function

Related