Siemens LU01 Transducer Scanning P725 to P729, P713 Echo Lock Window, P726 Level System Sync

Models: LU01

1 114
Download 114 pages 47.65 Kb
Page 68
Image 68

Parameters

Example:

Setting

P711 = 2, material agitator

P712 = 5:2

Result

a new reading will not be validated unless five consecutive measurements higher or two consecutive measurements lower than the current reading occur

Resetting P711 returns P712 to the respective preset values

P713 Echo Lock Window

Adjusts the size of the Echo Lock Window.

Values

Range: 0.000 to 9999

 

 

Preset: 0.000

 

 

 

 

Altered by

P003 Maximum Process Speed

 

 

 

Related

P005 Units

P711 Echo Lock

 

 

 

 

The Echo Lock Window is a distance window (units P005) centred on the echo and used to derive the Reading. When a new measurement is in the window, it is re-centred and the new Reading calculated. Otherwise, the new measurement is verified by Echo Lock (P711) before the reading is updated.

When 0 is entered the window is automatically calculated after each measurement. For slower P003 Maximum Process Speed values the window is narrow, for faster P003 values the window becomes wider.

Transducer Scanning (P725 to P729)

P726 Level System Sync

Enables the System Sync on the terminal block.

Values

0

 

not required

 

 

 

1

*

synchronize level monitors

 

 

 

 

 

Use this if another level measurement system is mounted nearby, and they are wired together on the Sync terminal.

P727 Scan Delay

The delay, in seconds, between measurements from transducer points .

Values

Range: 0.000 to 60.00

 

 

Preset: 5.0

 

 

 

 

Altered by

P003 Maximum Process Speed

 

 

 

Related

P001 Operation

 

 

 

Page 62

SITRANS LU01 – INSTRUCTION MANUAL

7ML19985BE02

Page 68
Image 68
Siemens LU01 Transducer Scanning P725 to P729, P713 Echo Lock Window, P726 Level System Sync, P727 Scan Delay, Example