Siemens LU01 Measurement Verification P710 to P713, P705 Rate Update Time, P707 Rate Value

Models: LU01

1 114
Download 114 pages 47.65 Kb
Page 66
Image 66

Parameters

P705 Rate Update Time

The time period (in seconds) over which the material level rate of change is averaged before Rate Value update.

Values

Range: 0.000 to 9999

 

 

 

Related

P707 Rate Value

 

 

 

P706 Rate Update Distance

The material level change (in metres) to initiate a Rate Value update.

Values

Range: 0.000 to 9999

 

 

 

Related

P707 Rate Value

 

 

 

P707 Rate Value

The rate of material level change (in Units (P005) or % of Span (P007) per minute).

Values

Range: -999 to 9999 (view only)

 

 

 

Altered By

P704 Rate Filter

 

 

 

Related

P005 Units

P007 Span

 

 

 

 

A negative rate indicates the vessel is emptying.

This is the value displayed when is pressed in RUN mode.

Measurement Verification (P710 to P713)

P710 Fuzz Filter

Use this to stabilize the reported level, due to level fluctuations (such as a rippling or splashing liquid surface) within the Echo Lock Window (P713).

Values

Range: 0 to 100 (0 = off)

 

 

Altered by

• P003 Maximum Process Speed

 

 

 

Related

P007 Span

P713 Echo Lock Window

 

 

 

 

This value (in % of Span, P007) is automatically altered when Maximum Process Speed (P003) is altered. The higher the value entered, the greater the fluctuation stabilized.

Page 60

SITRANS LU01 – INSTRUCTION MANUAL

7ML19985BE02

Page 66
Image 66
Siemens LU01 Measurement Verification P710 to P713, P705 Rate Update Time, P706 Rate Update Distance, P707 Rate Value