3.4.3 GENH/RM Rack Mounting outline drawings:
3.5 LOCATION, MOUNTING AND COOLING
This power supply is fan cooled. The air intake is at the front panel and the exhaust is at the rear
panel. Upon installation allow cooling air to each the front panel ventilation inlets. Allow minimum
10cm (4-inch) of unrestricted air space at the front and the rear of the unit.
The power supply should be used in an area that the ambient temperature does not exceed
+50°C.
3.6 AC SOURCE REQUIREMENTS
The Genesys
TM
series can be operated from a nominal 100V to 240V, single phase, 47i63 Hz.
The input voltage range and current required for each model is specified in Chapter 2. Ensure
that under heavy load, the AC voltage supplied to the power supply does not fall below the speci-
fications described in Chapter 2.
3.7 AC INPUT POWER CONNECTION
CAUTION
Connection of this power supply to an AC power source
should be made by an electrician or other qualified personnel
WARNING
There is a potential shock hazard if the power supply chassis
(with cover in place) is not connected to an electrical safety
ground via the safety ground in the AC input connector.