No.

Part name

 

Procedure

 

Remarks

 

 

 

 

 

Fan motor

1)

Perform the works in 1 of and 1 of .

Flange nut

 

 

2)

Take off flange nut fixing the fan motor with

Loosen by

 

 

 

 

the propeller fan.

 

turning clockwise.

 

 

 

 

 

 

• Loosen the flange nut by turning clock-

 

 

 

 

wise. (When tightening, turn it counter-

 

 

 

 

clockwise.)

 

 

3)Remove the propeller fan.

4)Remove connector for the fan motor from the inverter.

5)Take off fixing screws (4 pcs) with support-

ing the fan motor so that it does not fall

Propeller fan

down.

 

6)When replacing the fan motor at lower side, remove the motor lead fixed plate which is fixed to the partition plate with screw (ST1Tf4´10, 1 pc), pull the fan motor lead out of the partition plate, and then remove the fan motor.

* Cautions in assembling fan motor

 

<In case of RAV-SM1100AT-E>

Fan motor connector at upper side

• Be sure to mount the propeller fan and the

 

fan motor at upper and lower sides because

 

they are different.

 

• Tighten the flange nut with the following torque.

Upper side: 9.8N·m (100kgf·cm)

Lower side: 4.9N·m (50kgf·cm)

<In case of RAV-SM1400AT-E>

The same propeller fan and the fan motor are used at upper and lower sides.

Tighten the flange nut with the following

Cycle P.C. board

 

torque.

Fan motor connector at lower side

 

Upper side: 9.8N·m (100kgf·cm)

 

 

Lower side: 9.8N·m (100kgf·cm)

 

Be sure to mount the motor lead fixed plate

Fan motor

 

 

so that the fan motor lead is not caught in.

 

Be sure that the propeller fan does not come to contact with the fan motor lead.

Fan motor lead

Partition plate

Motor lead fixed plate