Error mode detected by outdoor unit
◎ : Flash, 〇 : Go on, ● : Go off
49
Wireless sensor | Wired remote | ||
lamp display | controller | ||
|
|
|
|
Operation | Timer | Ready | Check code |
|
|
|
|
|
|
| H01 |
● | ◎ | ● |
|
|
|
|
|
|
|
| H02 |
● | ◎ | ● |
|
|
|
|
|
|
|
| H03 |
● | ◎ | ● |
|
|
|
|
|
|
|
| L29 |
◎ | ○ | ◎ |
|
|
|
|
|
◎ | ○ | ◎ | L31 |
| |||
|
|
|
|
|
|
| P03 |
◎ | ● | ◎ |
|
|
|
|
|
|
|
| P04 |
◎ | ● | ◎ |
|
|
|
|
|
|
|
| P22 |
◎ | ● | ◎ |
|
|
|
|
|
◎ | ● | ◎ | P26 |
| |||
|
|
|
|
◎ | ● | ◎ | P29 |
| |||
|
|
|
|
◎ | ◎ | ○ | F04 |
| |||
|
|
|
|
◎ | ◎ | ○ | F06 |
| |||
|
|
|
|
◎ | ◎ | ○ | F08 |
| |||
|
|
|
|
Diagnostic function
Cause of operation
Breakdown of compressor
• Displayed when error is detected
Compressor does not rotate.
•
Current detection circuit error
•Current value at AC side is high even during
•Phase of power supply is missed.
Outdoor unit and other errors
•Communication error between CDB and IPDU
•Heat sink temperature error
(Detection of temperature over specified value)
Phase detection protective circuit operates. (Normal models)
Discharge temperature error
• Discharge temperature over specified value was detected.
Outdoor DC fan error
Inverter
IPDU position detection circuit error
Status of air conditioner
Stop
Stop
Stop
Stop
Operation continues. (Compressor stops.)
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Operation continues.
Condition
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Judgment and measures
1.Check power voltage. AC200V±20V
2.Overload operation of refrigerating cycle
3.Check current detection circuit at AC side.
1.Trouble of compressor (Compressor lock, etc.) : Replace compressor.
2.Defective cabling of compressor (Phase missing)
3.
1.Compressor immediately stops even if restarted. : Check IPDU.
2.
1.Check cables of CDB and IPDU.
2.Abnormal overload operation of refrigerating cycle
1.Check power phase order (Reversed phase)/phase missing.
2.Check outdoor P.C. board.
1.Check refrigerating cycle. (Gas leak)
2.Trouble of PMV
3.Check Td sensor.
1.Overload operation of refrigerating cycle
2.Check outdoor temperature sensor (TE).
3.Check outdoor CDB P.C. board.
1.Defective detection of position
2.
3.Lock of outdoor fan
4.Check outdoor CDB P.C. board.
1.Inverter immediately stops even if restarted. : Compressor motor rare short
2.Check IPDU. : Cabling error
1.Position detection circuit operates even if operating compressor by removing 3P connector. : Replace IPDU.
1.Check outdoor temperature sensor (TD).
2.Check outdoor CDB P.C. board.
1.Check outdoor temperature sensor (TE/TS).
2.Check outdoor CDB P.C. board.
1.Check outdoor temperature sensor (TO).
2.Check outdoor CDB P.C. board.
For an error mode detected in outdoor unit, the fan operates because sub unit of a group operation does not communicate with the outdoor unit.