Toshiba RAV-SM801BT-E, RAV-SM1400AT-E F06 error/18 error, F04 error/19 error, F08 error/1b error

Models: RAV-SM801BT-E RAV-SM561BT-E RAV-SM1401BT-E RAV-SM1100AT-E RAV-SM1101BT-E RAV-SM1400AT-E

1 126
Download 126 pages 63.42 Kb
Page 65
Image 65
[F06 error]/[18 error]

[F06 error]/[18 error]

Are connections of

TE/TS sensor connectors of CDB CN604/CN605 normal?

YES

Are characteristics of TE/TS sensor

resistance values normal?

YES

NO

Correct connection of connector.

* (For RAV-SM560AT-E, CN600 TE sensor and CN603 TS sensor)

NO

Replace TE and TS sensors.

Check CDB. Defect [F04 error]/[19 error] Replace

* Refer to Characteristics-3.

[F04 error]/[19 error]

Is connection of TD sensor connector

NO

 

of CDB CN600 normal?

 

YES

* (For RAV-SM560AT-E, CN601 TD sensor)

Correct connection of connector.

Are characteristics of TD sensor

resistance value normal?

YES

NO

Replace TD sensor.

Check control P.C. board. Defect [F08 error]/[1b error] Replace

* Refer to Characteristics-4.

[F08 error]/[1b error]

Is connection of TO sensor connector

of CDB CN601 normal?

YES

Are characteristics of TO sensor

resistance value normal?

YES

NO

*(For RAV-SM560AT-E, CN602 TO sensor)

NO

Correct connection of connector.

Replace TO sensor.

Check CDB. Defect Manual background Replace

* Refer to Characteristics-5.

63

Page 65
Image 65
Toshiba RAV-SM801BT-E, RAV-SM1400AT-E, RAV-SM1101BT-E F06 error/18 error, F04 error/19 error, F08 error/1b error