[P03 error]/[1E error]

Is protective control such as

NO

Are connections of

NO

 

 

discharge temprelease control normal?

 

cable/connector normal?

 

 

YES

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

Is charged refrigerant amount normal?

 

YES

 

 

 

YES

Is not abnormal overload?

 

 

 

NO

 

 

 

 

 

NO

Are characteristics of

 

TD sensor resistance value normal?

 

Correct the cabling and connection of connector.

Check parts. Defect Replace

Check and correct the charged refrigerant amount.

Improve and delete the cause

Replace TD sensor.

YES

* Refer to Characteristics-4.

Check CDB.

Defect Replace

* For RAV-SM560AT-E, replace control P.C. board.

[H01 error]/[1F error]

Is power voltage normal?

YES

Is not abnormal overload?

NO

Is the circuit detected by current sensor normal?

YES

NO

YES

NO

Improve power line.

Improve and delete the cause.

Check and correct circuit cables.

Check IPDU.

Defect Replace

* For RAV-SM560AT-E, replace control P.C. board.

65

Page 67
Image 67
Toshiba RAV-SM1101BT-E, RAV-SM1400AT-E, RAV-SM1100AT-E, RAV-SM1401BT-E, RAV-SM561BT-E P03 error/1E error, H01 error/1F error