9. OUTDOOR CONTROL

9-1. Outline of Main Controls

1.Pulse Modulating Valve (PMV) control

1)PMV is controlled with 50 to 500 pulses during operation, respectively.

2)In cooling operation, PMV is controlled with the temperature difference between TS sensor and TC sensor.

3)In heating operation, PMV is controlled with the temperature difference between TS sensor and TE sensor.

4)For the temperature difference in items 2) and 3), 1 to 5K is aimed as the target in both cooling and heating operations.

5)When the cycle excessively rose in both cooling and heating operations, PMV is controlled by TD sensor. The aimed value is usually 105°C for SM560 and 100°C for SM800, SM1100, SM1400 in both cooling and heating operations.

REQUIREMENT

A sensor trouble may cause a liquid back-flow or abnormal overheat resulting in excessive shortening of the compressor life. In a case of trouble on the compressor, be sure to check there is no error in the resistance value an the refrigerating cycle of each sensor after repair and then start the operation.

2. Discharge temperature release control

1) This function controls the operation frequency, that is, lowers the operation frequency when the dis-

TD [˚C]

 

charge temperature has not lower or the discharge

Error stop ("P03" display with 4 times of error counts)

 

temperature has rapidly risen during PMV control. It

a

 

 

subdivides the frequency control up to a unit of

 

b

Frequency down

 

0.6Hz to stabilize the cycle.

 

 

 

 

 

2) When the discharge temperature is detected in an

c

 

 

abnormal stop zone, the unit stops the compressor

 

 

 

Frequency holding

 

and restarts after 2 minutes 30 seconds. The error

 

 

 

 

 

counter is cleared when it has continued the opera-

d

 

 

tion for 10 minutes.

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency slow-up

 

If the abnormal stop zone has been detected by 4

 

 

 

(Up to command)

 

times without clearing of counter, an error ‘P03’ is

 

 

e

 

 

displayed.

 

 

 

 

 

 

 

 

 

 

 

 

 

As command is

 

* The cause is considered as excessively little amount

 

 

 

of refrigerant, defective PMV, or clogging of cycle.

 

 

 

 

 

 

 

 

[°C]

 

[A]

 

 

 

 

 

 

 

 

 

 

a

b

c

d

e

 

Frequency down

 

SM560

117

112

108

105

98

 

 

 

 

 

SM800, 1100, 1400

111

106

100

95

90

I1

Hold

 

 

 

 

 

 

 

 

 

 

3.

Current release control

 

 

 

 

1–0.5

Hold

 

 

 

 

Normal operation

 

The output frequency and the output voltage are

 

 

 

 

 

 

 

controlled by AC current value detected by T02 on the

 

 

 

outdoor P.C. board so that input current of the inverter

 

 

 

does not exceed the specified value.

 

 

 

 

 

Objective

SM560

SM800

SM1100

SM1400

model

COOL

HEAT

COOL

HEAT

COOL

HEAT

COOL

HEAT

 

 

 

 

 

 

 

 

 

I1 value [A]

9.22

11.93

12.00

13.43

18.90

19.65

19.65

19.65

 

 

 

 

 

 

 

 

 

* For the cooling only models, only COOL is objective.

40

Page 42
Image 42
Toshiba RAV-SM1400AT-E, RAV-SM1101BT-E Outdoor Control, Outline of Main Controls, Pulse Modulating Valve PMV control