No.

Part name

Procedure

Remarks

 

 

 

 

IPDU P.C. board 1) Perform the works in and .

Screw

Screw

2) Take off screws of the inverter assembly

 

 

to separate the inverter assembly.

 

 

(M4 × 8, 4 pcs)

 

 

3) Remove the connectors and the lead

 

 

wires which are connected from IPDU

 

 

P.C. board to the other parts.

 

 

1. Connector

 

 

CN04:

Connection with cycle P.C.

 

 

 

board (3P: White)

 

 

CN05:

Connection with cycle P.C.

 

 

 

board (2P: White) *(Note 1)

Screw

Screw

CN06:

Connection with cycle P.C.

 

 

 

board (5P: White)

 

 

CN13:

Connection with cycle P.C.

 

 

 

board (5P: Red) *(Note 1)

 

 

CN600: Heat sink sensor (2P: Black)

 

 

2. Lead wire

CN01:

Connection with power

 

 

terminal block (Red)

 

CN02:

Connection with power

 

 

terminal block (White)

 

CN03:

Connection with inverter box

IPDU P.C. board Heat sink cover

 

(Black)

 

CN09:

Connection with compressor

 

 

(Red)

 

CN10:

Connection with compressor

 

 

(White)

 

CN11:

Connection with compressor

 

 

(Black)

 

Rectifier diode

+ : Red lead wire *Note 2

: White lead wire *Note 2

Screw

~: Orange lead wire

(Top)

~: Brown lead wire

(Bottom)

Screw

*(Note 1)

 

Remove the connectors by releasing lock of

 

the housing.

Heat sink

4) Remove the heat sink cover.

P.C. board fixing hooks (5 positions)

(M4 × 8, 2pcs)

5) Take off two screws which fix the heat

IPDU P.C. board

sink and IGBT and also take off support

 

hooks of the P.C. board (5 positions) to

 

remove IPDU P.C. board.

 

6) Mount a new IPDU P.C. board.

*(Note 2)

The rectifier diode has polarity, so be careful to + and – . If + and – are mistaken, a trouble is caused.

110

Page 112
Image 112