DN

01

02

03

06

0F

10

11

12

13

14

19

1E

28

2A

2b

2E

30

31

32

40

5d

60

8b

Item

 

 

 

Description

 

At shipment

 

 

 

 

 

 

 

Filter sign lighting

0000

: None

 

0001

: 150H

According to type

time

0002

: 2500H

 

0003

: 5000H

 

 

 

0004

: 10000H

 

0005

: Clogged sensor used

 

 

 

 

 

 

 

 

 

 

Dirty state of filter

0000

: Standard

 

0001

: High degree of dirt

0000

: Standard

 

 

 

 

 

(Half of standard time)

 

 

 

 

 

 

 

 

 

 

Central control

0001

: No.1 unit

to

0064

: No.64 unit

0099

: Unfixed

address

0099

: Unfixed

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating suction temp

0000

: No shift

 

0001

: +1°C

0002

: +2°C

shift

0002

: +2°C

to

0010

: -10°C

(Floor type 0000: 0°C)

 

 

 

 

 

(Up to recommendation + 6)

 

 

 

 

 

 

 

 

 

 

Cooling only

0000

: Heat pump

 

0001

: Cooling only

0000

: Shared for cooling/

 

 

 

 

 

(No display of [AUTO] [HEAT])

 

heating

 

 

 

 

Type

0000

: (Air discharge cassette 1) 0001 : (Air discharge cassette 4) to 0037

According to model type

 

 

 

 

 

 

Indoor unit capacity

0000

: Unfixed

 

0001 to 0034

According to capacity type

 

 

 

 

 

 

 

 

Line address

0001

: No.1 unit

to

0030

: No.30 unit

0099

: Unfixed

 

 

 

 

 

 

 

 

Indoor unit address

0001

: No.1 unit

to

0064

: No.64 unit

0099

: Unfixed

 

 

 

 

 

 

 

 

Group address

0000

: Individual

 

0001

: Master of group

0099

: Unfixed

 

0002

: Sub of group

 

 

 

 

 

 

 

 

 

 

 

 

Flap type

0000

: No flap

 

0001

: Swing only

According to type

(Adjustment of air

0004

: 4-way

 

 

 

 

 

direction)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp difference of

0000

: 0 deg

to

0010

: 10 deg

0003

: 3 deg

automatic cooling/

(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)

 

(Ts±1.5)

heating mode

 

 

 

 

 

 

 

selection COOL

 

 

 

 

 

 

 

HEAT, HEAT COOL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Automatic reset of

0000

: None

 

0001

: Reset

0000

: None

power failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Option

 

 

 

 

 

0002

: Default

 

 

 

 

 

 

Thermo output

0000

: Indoor thermo ON

0001

: Output of outdoor comp-ON

0000: Thermo. ON

selection (T10 ƒ)

 

 

 

 

receiving

 

 

 

 

 

 

 

 

 

 

Option

 

 

 

 

 

0000

: Default

 

 

 

 

 

 

 

 

Option

 

 

 

 

 

0000

: Default

 

 

 

 

 

 

 

 

Option

 

 

 

 

 

0000

: Default

 

 

 

 

 

 

 

 

Sensor selection

0000

: Body TA sensor

 

0001

: Remote controller sensor

0000

: Body sensor

 

 

 

 

 

 

 

 

Option

 

 

 

 

 

0003

: Default

 

 

 

 

 

 

 

 

High ceiling selection

0000

: Standard filter

 

 

 

0000

: Standard

(Air volume selection)

0001

: Oil guard, Super-long life, Optical regenerative deodorization

 

 

 

0003

: High performance (65%), High performance (90%),

 

 

 

 

High antibacterial performance (65%)

 

 

 

 

 

 

 

 

 

Timer set

0000

: Available (Operable)

0001

: Unavailable (Operation prohibited)

0000

: Available

(Wired remote

 

 

 

 

 

 

 

controller)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Correction of high

0000

: None

 

0001

: Correction

0000

: None

heat feeling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 