No.

Part name

 

Procedure

Remarks

 

 

 

 

Drain pump

1.

Remove the drain pan and float switch.

Drain pump Drain pump holder

 

 

2.

Remove the set screws (3 positions) of

 

 

 

 

 

 

fixing drain pump plate and main unit.

 

 

 

3.

Remove the set screws (3 positions) of

 

 

 

 

fixing drain pump plate and drain pump.

 

 

 

 

 

6 -2

 

 

 

 

Screws (Fixing drain pump holder)

 

 

 

 

Screws (Fixing plate and drain pump)

 

 

6 -3

 

 

Drain pump holder

 

 

(6) -3. View from reverse side of drain pump

 

 

 

TC, TCJ sensor 1.

Remove the set screws (5 positions) and

Checking port cover (Right side)

 

check port cover (right side).

 

2.

Pull out the sensor is inserted into pipe of

 

 

the heat exchanger.

 

 

 

7

-1

 

 

Screws (Fixing check port cover (Right side))

 

 

 

 

ˆ Heat exchanger 1.

Take down the main unit and then treat

Check port cover (Left side)

 

 

the heat exchanger on the floor.

 

 

2.

Remove the drain pan.

 

 

3.

Remove the check port cover (right side).

 

 

4.

Remove the set screws (6 positions) and

 

 

 

check port cover (left side).

 

 

5.

Remove the set screws (2 positions) of

8

-4

 

fixing heat exchanger and main unit (left

 

 

 

 

side).

Screws (Fixing check port cover (Left side))

6.

Remove the set screws (7 positions) of

Screws (Fixing heat exchanger)

 

 

fixing heat exchanger and main unit (front

 

 

 

 

 

right side).

 

 

8 -5

Main unit (Left side)

Main unit (Front side)

8 -6

Screws

90

Page 92
Image 92
Toshiba RAV-SM1100AT-E, RAV-SM1400AT-E, RAV-SM1101BT-E, RAV-SM1401BT-E † Drain pump Remove the drain pan and float switch