[P22 error]/[1A error]

Are connections of CN301 and

 

CN300 of P.C. board correct?

 

 

 

YES

 

 

 

Does the fan rotate without trouble

NO

when handling the fan with hands under condition

 

of removing CN301 and CN300 from P.C. board?

 

 

 

YES

 

 

 

The status that the resistance values

 

between leads below are 50 to 80

 

for 40 motor (ICF-140-40) and 25 to 55

NO

for 60 motor (ICF-140-60-1) is normal.

 

Between

1

(Red lead) and 2

(White lead)

 

Between

2

(White lead) and

3

(Black lead)

 

Between

3

(Black lead) and

1

(Red lead)

 

of motor winding of connector (CN301)

 

 

 

YES

 

 

 

 

The status that there is

NO

5k to 20k

resistance values between

1 (Yellow lead) and 4 (Pink lead)

 

of motor position detection of

 

connector (CN300) is normal.

 

 

 

YES

 

 

 

CN301

CN300

*Connector of RAV-SM560AT-E differs from that of RAV-SM800AT-E, RAV-SM1100AT-E, RAV-SM1400AT-E.

CN300: Motor coil winding

CN301: Motor position detection

Normal fan motor

(Control or CDB P.C. board)

(Control P.C. board or CDB P.C. board)

NOTE :

Defective fan motor

However, GND circuit error inside of the motor is rarely detected even if the above check is carried out. When the circuit does not become normal even if P.C. board has been replaced, replace outdoor fan motor.

 

Single phase

Single phase

Single phase

 

RAV-SM560AT-E RAV-SM800AT-E

RAV-SM1100AT-E, SM1400AT-E

Objective P.C. board

Control P.C. board

CDB P.C. board

CDB P.C. board

Fan motor winding

CN300

CN301

CN301

Motor position detection

CN301

CN300

CN300

Fan motor winding

——

——

CN303

Motor position detection

——

——

CN302

59

Page 61
Image 61
Toshiba RAV-SM1101BT-E, RAV-SM1400AT-E, RAV-SM1401BT-E P22 error/1A error, Single phase, RAV-SM1100AT-E, SM1400AT-E