Toshiba RAV-SM1101BT-E, RAV-SM1400AT-E, RAV-SM1100AT-E Allocautions of fan tap revolutions rpm

Models: RAV-SM801BT-E RAV-SM561BT-E RAV-SM1401BT-E RAV-SM1100AT-E RAV-SM1101BT-E RAV-SM1400AT-E

1 126
Download 126 pages 63.42 Kb
Page 43
Image 43
Allocautions of fan tap revolutions [rpm]

4. Outdoor fan control (Object: SM800, SM1100, SM1400)

Allocautions of fan tap revolutions [rpm]

 

 

W1

W2

W3

W4

W5

W6

W7

W8

W9

WA

WB

WC

WD

WE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SM800

250

270

290

310

340

370

400

440

480

520

560

610

700

780

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SM1100

Upper fan

250

280

300

320

340

380

420

470

520

570

630

690

740

800

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lower fan

OFF

OFF

270

290

400

480

520

560

600

660

720

780

860

940

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SM1400

Upper fan

250

270

270

300

350

410

470

530

590

670

750

810

840

860

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lower fan

OFF

OFF

240

270

330

390

450

510

570

650

730

790

820

840

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1)Cooling fan control

The outdoor fan is controlled by TE sensor. (Cooling: Temperature conditions after medium term)

The cooling fan is controlled by every 1 tap of DC fan control (14 taps).

At the activation time, although the maximum fan tap in the following table are fixed for 60 seconds, after then the fan may not rotate with high speed for several minutes because the fan is controlled by TE sensor value. It is not an abnormal status.

ƒWhen the discharge temperature sensor is abnormal or the sensor comes off the holder, the fan does not rotate with high speed, but a protec- tive device works.

When the outdoor fan does not rotate with high speed, judge a fan error by comparing the control data in the following table with TO and TE values.

TE [˚C]

MAX.

46

+30 rpm / 20 sec.

37

Hold zone

34

–30 rpm / 20 sec.

20

MIN.

Control for fan tap by outdoor temperature in normal operation

TO

TO < 5°C

5 TO <10°C

10 TO < 15°C

15 TO < 20°C

20 TO < 25°C

25°C TO

TO error

 

 

 

 

 

 

 

 

MIN

W1

W2

W3

W4

W5

WA

W1

 

 

 

 

 

 

 

 

MAX

W6

W8

WA

WC

WE

WE

WE

 

 

 

 

 

 

 

 

2) Heating fan control

This control function lowers fan tap according to TE sensor value when outdoor temperature is high.

When a status TE > 20°C is detected continu- ously for 5 minutes, the operation may stop. This status does not output an error code and is assumed as usual status of thermo-OFF. The fan restarts after approx. 2 minutes 30 seconds and this intermittent operation is not a trouble.

ƒIf the status in item is frequently found, it is considered that the filter of suction part of the indoor unit is dirty. Clean the filter and restart the operation.

This control function does not work for 30 min- utes after activation, 1 minute after defrosting, and during defrost operation.

TE [˚C]

–60 rpm / 20 sec. STOP timer count

24

–60 rpm / 20 sec.

21

–30 rpm / 20 sec.

17

Hold zone

15

+30 rpm / 20 sec.

41

Page 43
Image 43
Toshiba RAV-SM1101BT-E, RAV-SM1400AT-E, RAV-SM1100AT-E, RAV-SM1401BT-E, RAV-SM561BT-E Allocautions of fan tap revolutions rpm