Error mode detected by remote controller or network adapter
◎ : Flash, 〇 : Go on, ● : Go off
50
Wireless sensor
lamp display
Operation | Timer | Ready |
|
|
|
— | — | — |
|
|
|
◎ | ● | ● |
|
|
|
◎ | ● | ● |
|
|
|
◎ | ● | ● |
|
|
|
◎ | ○ | ◎ |
|
|
|
— | — | — |
|
|
|
— | — | — |
|
|
|
— | — | — |
|
|
|
Wired remote
controller
Check code
No check code is displayed. (Remote controller does not operate.)
E01*2
E02
E09
L20
Central remote
controller
98
—
*3
Central remote
controller
99
—
*3
Central remote
controller
97
—
Central remote
controller
b7
| Diagnostic function |
|
|
| |
| Cause of operation | Status of air conditioner | Condition |
| Judgment and measures |
|
|
| |||
|
|
|
| ||
No communication with master indoor unit | Stop | — | Remote controller power error, Defective indoor EEPROM | ||
• | Remote controller cable is not correctly |
|
| 1. | Check remote controller |
| connected. |
|
| 2. | Check remote controller. |
• | Power of indoor unit is not turned on. |
|
| 3. | Check indoor power cables. |
• Automatic address cannot be completed. |
|
| 4. | Check indoor P.C. board. | |
|
|
|
| 5. | Check indoor EEPROM. (including socket insertion) |
|
|
|
|
| : Phenomenon of automatic address repetition occurred. |
|
|
|
| ||
No communication with indoor master unit | Stop | Displayed when | Signal receiving of remote controller is defective. | ||
• | Disconnection of | (Automatic restart) | error is detected | 1. | Check remote controller |
| remote controller and master indoor unit | * When there is center, operation |
| 2. | Check remote controller. |
| (Detected at remote controller side) | continues. |
| 3. | Check indoor power cables. |
|
|
|
| 4. | Check indoor P.C. board. |
Signal sending error to indoor unit | Stop | Displayed when | Signal sending of remote controller is defective. | ||
(Detected at remote controller side) | (Automatic restart) | error is detected | 1. | Check sending circuit inside of remote controller. | |
|
| * When there is center, operation |
|
| : Replace remote controller. |
|
| continues. |
|
|
|
Multiple master remote controllers are recognized. | Stop | Displayed when | 1. | Check there are multiple master units for 2 remote controllers | |
(Detected at remote controller side) | (Sub unit continues operation.) | error is detected |
| (including wireless). | |
|
|
|
|
| : Master unit is one and others are sub units. |
Duplicated indoor central addresses on | Stop | Displayed when | 1. | Check address setup of central control system network. | |
communication of central control system | (Automatic restart) | error is detected |
| (Network adapter SW01) | |
(Detected by central controller side) |
|
| 2. | Check network adapter P.C. board. | |
|
|
|
|
| |
Multiple network adapters on remote controller | Operation continues. | Displayed when | 1. | Check multiple network adapters. | |
communication line |
| error is detected | 2. | Check | |
(Detected by central controller side) |
|
|
| : Only one network adapter on remote controller communication line | |
|
|
|
|
| |
Interruption of central control system | Operation continues. | Displayed when | 1. | Check communication line/miscabling. Check power of indoor unit. | |
communication circuit | (According to handy remote controller) | error is detected | 2. | Check communication. (XY terminals) | |
(Detected by central controller side) |
|
| 3. | Check network adapter P.C. board. | |
|
|
|
| 4. | Check central controller (such as central control remote controller, etc.). |
|
|
|
| ||
Indoor Gr sub unit error | Continuation/stop | Displayed when | Check the check code of corresponding unit by handy remote controller. | ||
(Detected by central controller side) | (Based on a case) | error is detected |
|
| |
|
|
|
|
|
|
*2 Check code is not displayed by wired remote controller. (Usual operation of air conditioner is disabled.)
For wireless type models, E01 is notified by the display lamp.
*3 These errors are related to communication of remote controllers (A, B) and central system