[E10 error]/[CF error]

Check indoor control P.C. board (MCC-1402).

Defect Replace

[E18 error]/[97 error] *[99 error]

*: When central controller [99] is displayed, there are other causes of trouble.

NO

Is inter-unit cable of A and B normal?

YES

Correct inter-unit cable of remote controller.

Is there no disconnection

 

YES

 

 

 

 

 

 

 

 

 

 

 

Correct connection of connector.

 

or contact error of connector on harness

 

 

 

 

 

 

 

 

 

 

 

 

 

Check circuit cables.

 

from terminal block of indoor unit?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

NO

 

Is group control operation?

 

Is power of all indoor units turned on?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check indoor P.C. board (MCC-1402). Defect Replace

Check power connection of indoor unit. (Turn on power again.)

[E08, L03, L07, L08 error]/ *[96 error] [99 error]

*: When central controller [99] is displayed, there are other causes of trouble.

E08 : Duplicated indoor unit numbers

L03 : Two or more master units in a group control

L07 : One or more group addresses of [Individual] in a group control

L08 : Unset indoor group address (99)

If the above is detected when power has been turned on, the mode automatically enters in automatic ad- dress setup mode. (Check code is not displayed.)

However, if the above is detected during automatic address setup mode, the check code may be displayed.

[L09 error]/[46 error]

YES

Is capacity of indoor unit unset?

NO

Set capacity data of indoor unit. (Setup item code (DN) = 11)

Check indoor P.C. board (MCC-1402). Defect Replace

55