8-4. Indoor P.C. Board Optional Connector Specifications

Function

Connector

Pin

Specifications

Remarks

No.

No.

 

 

 

 

 

 

 

 

Option output

CN60

1

DC12V (COM)

 

 

 

 

 

 

 

 

2

Defrost output

ON during defrost operation of outdoor unit

 

 

 

 

 

 

 

3

Thermo. ON output

ON during Real thermo-ON (Comp ON)

 

 

 

 

 

 

 

4

Cooling output

ON when operation mode is in cooling system

 

 

 

 

(COOL, DRY, COOL in AUTO cooling/heating)

 

 

 

 

 

 

 

5

Heating output

ON when operation mode is in heating system

 

 

 

 

(HEAT, HEAT in AUTO cooling/heating)

 

 

 

 

 

 

 

6

Fan output

ON during indoor fan ON

 

 

 

 

(Air purifier is used/Interlock cable)

 

 

 

 

 

Outside error

CN80

1

DC12V (COM)

(When continued for 1 minute)

input

 

 

 

Check code “L30” is output and forced operation stops.

 

2

DC12V (COM)

 

 

 

 

 

 

 

 

 

 

3

Outside error input

 

 

 

 

 

 

Filter option

CN70

1

Filter/Option/Humidifier

Option error input is controlled. (Protective operation

error

 

 

setup input

for device attached to outside is displayed.)

 

 

 

 

 

 

 

2

0V

* Setting of option error input is performed from

 

 

 

 

remote controller. (DN=2A)

 

 

 

 

 

CHK

CN71

1

Check mode input

Used for operation check of indoor unit. (Communica-

Operation check

 

 

 

tion with outdoor unit or remote controller is not

 

 

2

0V

performed, but the specified operation such as indoor

 

 

fan “H” or drain pump ON is output.)

 

 

 

 

 

DISP display

CN72

1

Display mode input

Display mode enables indoor unit and remote control-

mode

 

 

 

ler to communicate. (When power is turned on)

 

2

0V

 

 

 

 

 

 

 

 

EXCT demand

CN73

1

Demand input

Forced thermo-OFF operation in indoor unit

 

 

 

 

 

 

 

2

0V

 

 

 

 

 

 

39

Page 41
Image 41
Toshiba RAV-SM801BT-E Indoor P.C. Board Optional Connector Specifications, Function Connector Pin Specifications Remarks