Toshiba RAV-SM1401BT-E, RAV-SM1400AT-E, RAV-SM1101BT-E, RAV-SM561BT-E Address Setup & Group Control

Models: RAV-SM801BT-E RAV-SM561BT-E RAV-SM1401BT-E RAV-SM1100AT-E RAV-SM1101BT-E RAV-SM1400AT-E

1 126
Download 126 pages 63.42 Kb
Page 87
Image 87
13-2. Address Setup & Group Control

13-2. Address Setup & Group Control

<Terminology>

Indoor unit No. : N - n = Outdoor unit line address N (Max. 30) - Indoor unit address n (Max. 64)

Group address : 0

= Individual (Not group control)

1

= Master unit in group control

2

= Sub unit in group control

Master unit (= 1) : The representative of multiple indoor units in group operation sends/receives signals to/from the remote controllers and sub indoor units. (* It has no relation with an indoor unit which communicates serially with the outdoor units.)

The operation mode and setup temperature range are displayed on the remote controller LCD. (Except sir direction adjustment of flap)

Sub unit (= 2) : Indoor units other than master unit in group operation

Basically, sub units do not send/receive signals to/from the remote controllers. (Except errors and response to demand of service data)

13-2-1. System configuration

1. Single

2. Single group operation

Outdoor

 

 

 

 

 

 

 

 

Indoor

 

1-1

 

(Master/Sub)

2-1

 

Individual

Sub

 

 

 

 

 

 

 

 

Remote

 

 

 

 

 

 

 

 

 

 

 

 

controller

 

 

 

 

 

1-1

Sub

4-1

Master

3-1

Sub

8-1

Sub

13-2-2. Automatic address example from unset address (No miscabling)

1. Standard (One outdoor unit)

 

 

 

 

 

1) Single

2) Gr operation

 

(Multiple outdoor units = Miltiple indoor units only with serial

 

communication)

 

 

 

 

 

 

 

 

 

 

 

 

1-1

Individual

(Master/Sub)

2-1

Sub

1-1

Sub

4-1

Master

8-1

Sub

Max. 8 units

Manual backgroundManual background Only turning on source power supply (Automatic completion) Manual backgroundManual background