7-3. Tools

7-3. Tools

7-3-1. Required Tools

The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.

The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.

(1)Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))

(2)Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)

(3)Tools commonly used for R410A and for conventional refrigerant (R22)

The table below shows the tools exclusive for R410A and their interchangeability.

Tools exclusive for R410A (The following tools for R410A are required.)

Tools whose specifications are changed for R410A and their interchangeability

 

 

 

R410A

Conventional air

 

 

 

air conditioner installation

conditioner installation

No.

Used tool

Usage

 

 

 

Existence of

Whether conven-

Whether new equipment

 

 

 

 

 

 

new equipment

tional equipment

can be used with

 

 

 

for R410A

can be used

conventional refrigerant

 

 

 

 

 

 

Flare tool

Pipe flaring

Yes

*(Note 1)

¡

 

Copper pipe gauge for

Flaring by conventional

 

*(Note 1)

*(Note 1)

adjusting projection

Yes

flare tool

 

margin

 

 

 

 

ƒ

Torque wrench

Connection of flare nut

Yes

X

X

 

 

 

 

 

 

Gauge manifold

Evacuating, refrigerant

Yes

X

X

 

 

Charge hose

charge, run check, etc.

 

 

 

 

 

 

 

 

 

 

Vacuum pump adapter

Vacuum evacuating

Yes

X

¡

Electronic balance for

Refrigerant charge

Yes

X

¡

refrigerant charging

 

 

 

 

 

 

ˆ

Refrigerant cylinder

Refrigerant charge

Yes

X

X

Leakage detector

Gas leakage check

Yes

X

¡

Š

Charging cylinder

Refrigerant charge

(Note 2)

X

X

(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.

(Note 2) Charging cylinder for R410A is being currently developed.

General tools (Conventional tools can be used.)

In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools.

(1)

Vacuum pump

(4) Reamer

(9)

Hole core drill (Ø65)

 

Use vacuum pump by

(5)

Pipe bender

(10)

Hexagon wrench

 

attaching vacuum pump adapter.

 

(6)

Level vial

 

(Opposite side 4mm)

(2)

Torque wrench

 

(7)

Screwdriver (+, –)

(11)

Tape measure

(3)

Pipe cutter

 

 

(8)

Spanner or Monkey wrench

(12)

Metal saw

 

 

 

 

 

 

Also prepare the following equipments for other installation method and run check.

(1)

Clamp meter

(3)

Insulation resistance tester

(2)

Thermometer

(4)

Electroscope

27