Toshiba RAV-SM1100AT-E, RAV-SM1400AT-E, RAV-SM1101BT-E P19 error/08 error, F02 error/0d error

Models: RAV-SM801BT-E RAV-SM561BT-E RAV-SM1401BT-E RAV-SM1100AT-E RAV-SM1101BT-E RAV-SM1400AT-E

1 126
Download 126 pages 63.42 Kb
Page 62
Image 62

[P19 error]/[08 error]

NO

Check and replace electron expansion valve.

NO

Is operation of

4-way valve normal?

YES

Is flow of refrigerant by electron expansion valve normal?

YES

Are characteristics

of TC sensor resistance

value normal?

NO

Is voltage applied

NO

 

to 4-way valve coil terminal

 

 

in heating operation?

 

 

YES

 

 

 

 

Check 4-way valve

Defect Replace

NO

Is circuit cable normal?

YES

Check and correct circuit.

*Refer to Characteristics-2. YES

Replace TC sensor.

Check indoor P.C. board.

Defect Replace

NO

Check CDB P.C. board.

YES

Check CDB P.C. board.

Defect Replace

* For RAV-SM560AT-E, check control P.C. board.

In cooling operation, if high pressure is abnormally raised, [P19 error]/[08 error] may be displayed. In this case, remove cause of pressure up and then check again referring to the item [P04 error]/[21 error].

[F02 error]/[0d error]

Is connection of TC sensor connector

NO

 

(Indoor P.C. board CN101) normal?

 

 

YES

 

 

 

 

 

 

Correct connection of connector.

Are characteristics of

TC sensor resistance value normal?

YES

Check indoor P.C. board (MCC-1402).

Defect Replace

NO

* Refer to Characteristics-2.

Replace TC sensor.

60

Page 62
Image 62
Toshiba RAV-SM1100AT-E, RAV-SM1400AT-E, RAV-SM1101BT-E, RAV-SM1401BT-E, RAV-SM561BT-E P19 error/08 error, F02 error/0d error