Item

Outline of specifications

Remarks

 

 

 

DAfter-heat elimi-

When heating operation stops, the indoor fan operates

 

nation

with LOW mode for approx. 30 seconds.

 

Frequency fixed

<In case of wired remote controller>

 

operation

1.

When pushing [CHECK] button for 4 seconds or more,

 

(Test run)

 

 

[TEST] is displayed on the display screen and the

 

 

 

mode enters in Test run mode.

 

 

2.

Push [ON/OFF] button.

 

 

3.

Using [MODE] button, change the mode from [COOL]

 

 

 

to [HEAT].

 

 

 

• Do not use other mode than [COOL]/[HEAT] mode.

 

 

 

During test run operation, the temperature cannot

 

 

 

 

be adjusted.

 

 

 

An error is detected as usual.

 

 

 

A frequency fixed operation is performed.

 

 

4.

After the test run, push [ON/OFF] button to stop the

 

 

 

operation. (Display in the display part is same as the

 

 

 

procedure in item 1).)

 

 

5.

Push [CHECK] button to clear the test run mode.

 

 

 

([TEST] display in the display part disappears and the

 

 

 

status returns to the normal stop status.)

 

 

 

 

 

Central control

1)

Setting at the central controller side enables to select

 

mode selection

 

the contents which can be operated on the remote

 

 

 

controller at indoor unit side.

 

 

2)

RBC-AMT21

 

 

 

[Last push priority] :

(No display)

 

 

The operation contents can be selected from both

 

 

 

remote controller and central controller of the indoor unit

 

 

 

side, and the operation is performed with the contents

 

 

 

selected at the last.

 

 

 

[Center] :

[CENTER] goes on.

 

 

Start/Stop operation only can be handled on the remote

 

 

 

controller at indoor unit side.

 

 

 

[Operation Prohibited] :

[CENTER] goes on.

 

 

It cannot be operated on the remote controller at indoor

In a case of wireless

 

 

unit side. (Stop status is held.)

type, the display lamp

 

 

 

 

does not change.

 

 

 

 

However, contents which

 

 

 

 

can be operated are

 

 

 

 

same.

 

 

 

 

The status set in [CEN-

 

 

 

 

TER]/[Operation Prohib-

 

 

 

 

ited] mode is notified with

 

 

 

 

the receiving sound “Pi,

 

 

 

 

Pi, Pi, Pi, Pi” (5 times).

36

Page 38
Image 38
Toshiba RAV-SM1100AT-E, RAV-SM1400AT-E Case of wired remote controller, Last push priority, Center, Operation Prohibited