Toshiba RAV-SM1101BT-E, RAV-SM1400AT-E 7 8 9, Item, Outline of specifications, Remarks

Models: RAV-SM801BT-E RAV-SM561BT-E RAV-SM1401BT-E RAV-SM1100AT-E RAV-SM1101BT-E RAV-SM1400AT-E

1 126
Download 126 pages 63.42 Kb
Page 37
Image 37
7

No.

7

8

9

Item

 

 

 

Outline of specifications

 

 

Remarks

 

 

 

 

 

Freeze preven-

1) The cooling operation (including Dry operation) is

 

 

Tcj : Indoor heat ex-

tive control

performed as follows based on the detected tempera-

changer sensor

(Low tempera-

ture of Tc sensor or Tcj sensor.

 

 

temperature

ture release)

When [J] zone is detected for 6 minutes (Following

 

 

 

 

figure), the commanded frequency is decreased from

 

 

the real operation frequency. After then the commanded

 

 

frequency changes every 30 seconds while operation is

 

 

performed in [J] zone.

 

 

 

 

 

 

 

 

In [K] zone, time counting is interrupted and the opera-

 

 

tion is held.

 

 

 

 

 

 

 

 

 

When [I] zone is detected, the timer is cleared and the

 

 

operation returns to the normal operation.

 

 

 

 

If the commanded frequency becomes S0 because the

 

 

operation continues in [J] zone, the return temperature

 

 

A is raised from 5°C to 12°C until [I] zone is detected

 

 

and the indoor fan operates with [M] mode.

 

 

[M] mode :

 

 

 

 

(˚C)

 

 

 

 

 

 

 

Air speed selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

I

 

 

A

 

 

 

 

 

 

 

 

 

K

 

 

 

 

 

2

 

J

 

 

 

 

 

 

 

 

 

 

 

 

 

In heating operation, the freeze-preventive control

 

 

 

 

works if 4-way valve is not exchanged and the condition

 

 

is satisfied. (However the temperature for J zone

 

 

 

 

dashing control is changed from 2°C to –5°C.)

 

 

 

 

 

 

 

High-temp

1) The heating operation is performed as follows based on

 

release control

the detected temperature of Tc sensor or Tcj sensor.

 

 

When [M] zone is detected, the commanded fre-

 

 

 

 

 

quency is decreased from the real operation fre-

 

 

 

 

 

quency. After then the commanded frequency

 

 

 

 

 

changes every 30 seconds while operation is per-

 

 

 

formed in [M] zone.

 

 

 

 

 

 

 

 

In [N] zone, the commanded frequency is held.

 

 

 

 

When [L] zone is detected, the commanded fre-

 

 

 

 

 

quency is returned to the original value by approx.

 

 

 

6Hz every 60 seconds.

 

 

 

 

 

 

 

 

Setup at

 

 

Tc (˚C)

M

 

 

shipment

Control temp (°C)

Tcj A

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

A

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

56 (54)

52 (52)

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE :

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When the operation has started or when Tc or Tcj became

Same when thermostat is

 

lower than 30°C after start of the operation, temperature is

turned off.

 

controlled between values in parentheses of A and B.

 

 

 

 

 

 

Drain pump

1) In cooling operation (including Dry operation), the drain

 

control

pump is usually operated.

 

 

 

 

 

 

 

2)If the float switch operates while drain pump operates, the compressor stops, the drain pump continues the operation, and a check code is output.

3)If the float switch operates while drain pump stops, the compressor stops and the drain pump operates. If the

float switch keeps operating for approx. 4 minutes, a

 

check code is output.

Check code [P10]