Toshiba RAV-SM1100AT-E, RAV-SM1400AT-E, RAV-SM1101BT-E, RAV-SM1401BT-E E04 error/04 error

Models: RAV-SM801BT-E RAV-SM561BT-E RAV-SM1401BT-E RAV-SM1100AT-E RAV-SM1101BT-E RAV-SM1400AT-E

1 126
Download 126 pages 63.42 Kb
Page 56
Image 56
[E04 error]/[04 error]

[E04 error]/[04 error]

NO

Does outdoor unit operate?

YES

NO

Is setup of group address correct?

YES

Are 1, 2, 3 inter-unit cables normal?

NO

 

 

 

YES

 

 

 

 

 

 

Are connections from connectors

NO

of inter-terminal blocks (1, 2, 3)

 

 

of indoor/outdoor units normal?

 

 

YES

 

 

 

 

 

 

Check item code [14].

Correct inter-unit cable.

Correct connection of connector.

 

 

 

 

 

 

Does voltage between

NO

 

 

Check indoor P.C. board

 

2 and 3 of inter-terminal blocks (1, 2, 3)

 

 

 

(MCC-1402).

 

 

of indoor unit vary?*

 

 

 

Defect Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

*As shown in the following figure, perform measurement within 20 seconds after power ON.

S5277G

Black

3

White

2

1

Inter-terminal block

For RAV-SM560AT-E, main circuit on control P.C. board

Is DC280V applied between

NO

terminals of electrolytic capacitor

 

 

of IPDU main circuit?

 

For RAV-SM560AT-E,

 

YES

 

 

 

 

 

 

check case thermo.

 

 

 

 

 

 

 

 

 

 

 

Replace IPDU.

Check indoor P.C. board (MCC-1402 or MCC-1403). Defect Manual background Replace Check CDB.

Defect Manual background Replace

Is DC7V power supplied to CDB?

Are cablings between Pin 2 and Pin 5

of CN800 and between IPDU

and CDB normal?

YES

Is case thermo (CN500) connected?

YES

NO

Does case thermo operate?

YES

Check/Correct charged refrigerant amount.

NO

NO

Replace IPDU.

Correct connection of connector.

Correct connection of connector.

54

Page 56
Image 56