![Reading the](/images/new-backgrounds/49489/49489203x1.webp)
Terminal Unit
Control (TUC)
Table 40. Blink Sequence Corresponding Diagnostic Codes
Sequence 1 | Sequence 2 | Sequence 3 |
|
|
|
1 2 3 4 | 1 2 3 4 | 1 2 3 4 | Code | Diagnostic | Latch |
|
|
| None | Power failure | None |
|
|
| None | Controller failure | None |
ϒ ϒ ϒ ϒ | ϒ ϒ ϒ ϒ | ϒ ϒ ϒ ϒ | 00 | None | N/A |
ϒ ϒ ϒ ϒ | λ ϒ ϒ ϒ | λ ϒ λ λ | 8B | Condensate overflow | Yes |
ϒ ϒ ϒ ϒ | λ ϒ ϒ λ | λ ϒ λ λ | 9B | Leaving water temp | No |
|
|
|
| sensor 1 failure |
|
ϒ ϒ ϒ ϒ | λ ϒ λ ϒ | ϒ ϒ ϒ ϒ | A0 | Zone and supply temp | No |
|
|
|
| sensor failure |
|
ϒ ϒ ϒ ϒ | λ λ ϒ ϒ | λ ϒ ϒ ϒ | C8 | High EWT | No |
ϒ ϒ ϒ ϒ | λ λ ϒ ϒ | λ ϒ λ λ | CB | Low EWT | No |
ϒ ϒ ϒ ϒ | λ λ ϒ ϒ | λ λ λ λ | CF | Low temp. detect. or | Yes |
|
|
|
| condensate overflow |
|
ϒ ϒ ϒ ϒ | λ λ ϒ λ | ϒ ϒ λ λ | D3 | Low discharge air temp | Yes |
ϒ ϒ ϒ ϒ | λ λ ϒ λ | ϒ λ ϒ ϒ | D4 | Smoke alarm | Yes/No |
ϒ ϒ ϒ ϒ | λ λ ϒ λ | ϒ λ ϒ λ | D5 | High dischg air temp | Yes/No |
ϒ ϒ ϒ ϒ | λ λ ϒ λ | λ λ ϒ λ | DD | Low fresh air temp | No |
ϒ ϒ ϒ ϒ | λ λ λ λ | λ ϒ ϒ ϒ | F8 | Bad configuration | No |
ϒ ϒ ϒ ϒ | λ λ λ λ | λ λ λ ϒ | FE | Return air high limit | Yes |
|
|
|
|
|
|
Reading the
Operating
Machine State
Use the human interface to read the unit operating machine state.
1.Read and record the initial TUC address.
2.Set the TUC DIP switch #5 and #8 to ON (address = 9). The remaining switches will be off.
3.Short and hold the test input.
4.The LEDs will blink to define an operating machine state. The operating machine state information will be displayed in a series of three blink sequences.
Sequence 1: When the test input is shorted continuously all LEDs go off for one second.
Sequence 2: LED #5 will light to indicate that sequence 2 is currently being displayed. LEDs one through four will display the first part of the operating machine state.
Sequence 3: LED #6 will light to indicate that sequence 3 is currently being displayed. LEDs one through four will display the second part of the operating machine state.
5.Reference Table 25 on page 75 to interpret the operating machine state derived from the blink sequences.
102 |