2.Position and install the suspension rods or a suspension device (supplied by installer) according to the unit size dimensions in Figure 4 on page 15. Also refer to the weight range chart given in Table 1.
3. On cabinet units, remove the bottom panel by using a 5/32 inch Allen wrench to unscrew fasteners. Swing the panel down and lift outward.
4.Level the unit by referencing the chassis end panels. Adjust the suspension device.
5.Complete piping and wiring connections, in addition to any neces sary ductwork as instructed in the following sections. Ensure that the auxiliary drain pan is in position on
6.Install the bottom panel before starting the unit.
7.Ensure condensate drain line is pitched 1 inch per 10 feet of pipe away from
Table 1. Unit Operating Weights, pounds (kg) |
|
|
|
| ||||
Unit | Cabinet | Concealed | Recessed | Low Vertical | Low Vertical | |||
Size | Models | Models | Models | Cabinet Models | Concealed | |||
|
|
|
|
|
|
| Models | |
02 | 84 | (38) | 68 (31) | 68 (31) | NA |
| NA |
|
03 | 84 | (38) | 68 (31) | 68 (31) | 112 (51) | 96 | (44) | |
04 | 112 (51) | 96 (44) | 78 (35) | 139 | (63) | 123 (56) | ||
06 | 139 (63) | 123 (56) | 118 (54) | 148 | (67) | 131 (59) | ||
08 | 148 (67) | 131 (59) | 129 (59) | NA |
| NA |
| |
10 | 200 (91) | 182 (83) | 243 (110) | NA |
| NA |
| |
12 | 200 | (91) | 182 (83) | 243 (110) | NA |
| NA |
|
Note: All weights are approximate. Individual weights may vary depending upon the unit’s options.