Trane LO manual Installation Checklist

Models: LO

1 136
Download 136 pages 3.51 Kb
Page 13
Image 13
Installation Checklist

Installation Checklist

The following checklist is only an abbreviated guide to the detailed installation procedures given in this manual. Use this list to ensure all necessary procedures are complete. For more detailed information, refer to the appropriate sections in this manual.

!WARNING: Allow rotating fan to stop before servicing equipment. Failure to do so may cause severe personal injury or death.

ο

ο

1.Inspect the unit for shipping damage.

2.Level installation location to support the unit weight ad-

equately. Make all necessary wall or ceiling openings to allow adequate air flow and service clearances.

ο3. Ensure the unit chassis is level.

!CAUTION: The unit must be installed level (zero tolerance) in both horizontal axis for proper operation. Failure to do so may result in condensate management problems such as standing water inside the unit. Stand- ing water and wet surfaces may result in microbial growth (mold) in the drain pan that may cause unpleasnt odors and serious health-related indoor air quality prob- lems.

ο4. Secure the unit and any accessory items properly to the wall or ceiling support rods.

ο5. Complete piping connections correctly.

ο6. Check field sweat connections for leaks and tighten the valve stem packing, if necessary.

ο7. Install the auxiliary drain pan properly under piping package on fan-coil units.

ο8. Pitch condensate drain line 1 inch drop per 10 feet of line run on fan-coil units.

UNT-IOM-6

13