Tracer® ZN.520

Occupied

When the controller is in the occupied mode, the unit attempts to maintain the space temperature at the active occupied heating or cooling setpoint, based on the measured space temperature, the discharge air temperature, the active setpoint, and the proportional/ integral control algorithm. The modulating control algorithm used when occupied or in occupied standby is described in the following sections. Additional information related to the handling of the control- ler setpoints can be found in the previous Setpoint operation section.

Unoccupied Mode

When the controller is in the unoccupied mode, the controller at- tempts to maintain the space temperature at the stored unoccupied heating or cooling setpoint, based on the measured space tempera- ture, the active setpoint and the control algorithm, regardless of the presence of a hardwired or communicated setpoint. Similar to other configuration properties of the controller, the locally stored unoccu- pied setpoints can be modified using Rover™ service tool.

In unoccupied mode, a simplified zone control algorithm is run. During the cooling mode, when the space temperature is above the cool setpoint, the primary cooling capacity operates at 100%. If more capacity is needed, the supplementary cooling capacity turns on (or opens to 100%). During the heating mode, when the space tempera- ture is below the heat setpoint, the primary heating capacity turns on. All capacity is turned off when the space temperature is between the unoccupied cooling and heating setpoints. Note that primary heating or cooling capacity is defined by unit type and whether heating or cooling is enabled or disabled. For example, if the economizer is enabled and possible, it will be the primary cooling capacity. If hydronic heating is possible, it will be the primary heating capacity.

Occupied Standby Mode

The controller can be placed into the occupied standby mode when a communicated occupancy request is combined with the local (hardwired) occupancy binary input signal. When the communicated occupancy request is unoccupied, the occupancy binary input (if present) does not affect the controller’s occupancy. When the communicated occupancy request is occupied, the controller uses the local occupancy binary input to switch between the occupied and occupied standby modes.

During occupied standby mode, the controller’s economizer damper position goes to the economizer standby minimum position. The economizer standby minimum position can be changed using Rover service tool.

In the occupied standby mode, the controller uses the occupied

62

UNT-IOM-6

Page 62
Image 62
Trane LO manual Unoccupied Mode, Occupied Standby Mode

LO specifications

Trane LO is a cutting-edge solution in the HVAC sector, designed with advanced engineering and smart technologies to meet diverse climate control needs. Renowned for its reliability and efficiency, Trane LO offers a wide array of features that set it apart in the market.

One of the core characteristics of Trane LO is its energy efficiency. Equipped with variable speed compressors, the system can adjust its output according to the cooling or heating demand, ensuring optimal energy use. This feature not only reduces energy consumption but also lowers utility bills for users. Additionally, Trane LO units often come with a SEER (Seasonal Energy Efficiency Ratio) rating that ensures top performance during hotter months.

Incorporating state-of-the-art technology, Trane LO features Smart Technology integration. Through IoT (Internet of Things) capabilities, users can monitor and control their HVAC systems remotely via smartphones or smart home devices. This feature promotes convenience and ensures that energy use can be optimized from anywhere, giving users greater control over their indoor climate.

Another standout technology in Trane LO is its use of environmentally friendly refrigerants. The system is designed to utilize low-GWP (Global Warming Potential) refrigerants, making it compliant with modern environmental standards and contributing to a greener planet.

The Trane LO also emphasizes durability. Constructed with high-quality materials, including weather-resistant finishes, these units are built to withstand various environmental conditions, ensuring they maintain peak performance over the years.

Noise reduction is another critical aspect of the Trane LO line. With features such as sound blankets and vibration dampening technology, the units operate quietly, ensuring that the comfort of users is not compromised by disruptive noise levels.

Maintenance is simplified with the Trane LO, as several units are engineered for easy access to essential components, promoting hassle-free servicing. This is vital for prolonging the lifespan of the system and reducing maintenance costs.

In summary, Trane LO represents a fusion of energy efficiency, advanced technology, environmental responsibility, durability, and user-friendly features. Whether for residential or commercial applications, Trane LO systems stand as a reliable choice for effective climate control.