Fan Mode Switch

Fan Mode Switch

Manual Fan Mode Switch

The manual fan mode switch is available for fan-coil units that do not have Trane factory-mounted control packages. This four-position switch (off-hi-med-lo) allows manual fan mode selection and is available unit or wall mounted.

The unit-mounted option (Digit 31 = D) operates on line voltage. The wall-mounted option (Digit 31 = K) is low-voltage and has three 24 volt relays using a factory-wired transformer and relays to control the fan motor.

Sequence of Operations

Off: Fan is turned off, two-position damper option spring-returns closed.

Hi, Med, Lo: Fan runs continuously at the selected speed. The two- position damper option opens to an adjustable mechanical stop- position.