Tracer® ZN.520
Zone Sensor
Space Temperature Measurement
The Tracer® ZN.520 controller accepts the following zone sensor module inputs:
•Space temperature measurement (10kW thermistor)
•Local setpoint (either internal or external on the zone sensor module)
•Fan switch
•Timed override (On) and Cancel timed override
•Communication jack
Trane zone sensors use a 10kW thermistor to measure the space temperature. Typically, zone sensors are
External Setpoint Adjustment | Zone sensors with an external setpoint adjustment (1kW) provide the |
| Tracer® ZN.520 controller with a local setpoint (50 to 85 F or 10 to |
| 29.4 C). The external setpoint is exposed on the zone sensor’s front |
| cover. |
| When the hardwired setpoint adjustment is used to determine the |
| setpoints, all unit setpoints are calculated based on the hardwired |
| setpoint value, the configured setpoints, and the active mode of the |
| controller. The hardwired setpoint is used with the controller’s occu- |
| pancy mode (occupied, occupied standby, or unoccupied), the |
| heating or cooling mode, the temperature deadband values, and the |
| heating and cooling setpoints (high and low limits) to determine the |
| controller’s active setpoint. |
When a building automation system or other controller communicates a setpoint to the controller, the controller ignores the hardwired setpoint input and uses the communicated value. The exception is the unoccupied mode, when the controller always uses the stored default unoccupied setpoints. After the controller completes all setpoint calculations, based on the requested setpoint, the occu- pancy mode, the heating and cooling mode, and other factors, the calculated setpoint is validated against the following setpoint limits:
•Heating setpoint high limit
•Heating setpoint low limit
•Cooling setpoint high limit
•Cooling setpoint low limit
76 |