Tracer® ZN.520
Tracer® ZN.520 Unit Start-Up
Tracer® Communications
Tracer® ZN.520
Sequence of
Operation
Refer to the Trane publication,
Follow the procedure below to operate the Tracer® ZN.520 in a stand- alone operation:
1)Turn power on at the disconnect switch option.
2)Position the fan mode switch to either high, medium, low, or the auto position.
3)Rotate the setpoint dial on the zone sensor module to 55 F for cooling or 85 F for heating.
The appropriate control valve will actuate assuming the following conditions:
1)Room temperature should be greater than 55 deg. F and less than 85 deg. F
2)For a
requested and cold water (5 degrees lower than room tem perature) flows into the unit.
4)Select the correct temperature setpoint.
Note: Select and enable zone sensor temperature settings to prevent freeze damage to unit.
Tracer® ZN.520 is a Comm 5 controller. There is no need to set an address. Each individual board has its own unique Neuron I.D. number that takes the place of dip switches.
The Tracer® ZN.520 operates the fan in the following modes:
1)occupied
2)unoccupied
3)occupied standby
4)occupied bypass
5)Tracer Summit with supply fan control
61 |