Trane LO Yellow COMM LED, Tracer ZN.010 and ZN.510, Green STATUS LED Activity, Description

Models: LO

1 136
Download 136 pages 3.51 Kb
Page 47
Image 47
Green STATUS LED

Tracer® ZN.010

and ZN.510

Green STATUS LED

The green LED normally indicates whether the controller is powered on (24 VAC supplied). Reference Table 11.

Table 11. Green STATUS LED Activity

Green LED Blink Activity

Description

LED on continuously

Power on (normal operation)

LED blinks once

Manual output test mode

LED blinks twice

Manual output test mode, with one or more diagnos-

 

tic present

LED blinks (1/4 second on, 1/4 second

 

off for 10 seconds)

“Wink” mode

LED off

· Power off

 

· Abnormal condition

 

· Test button is pressed

Note: The “wink” feature allows the identification of a particular controller. When sending a request from a device, such as Rover™, the controller will “wink” to indicate it received the signal.

Yellow COMM LED

Table 12. Yellow COMM LED Activity

Yellow LED Blink Activity

Description

LED off continuously

The controller is not detecting any communication.

 

(Normal for units in standalone applications)

LED blinks

The controller detects communication.

LED on continuously

Abnormal condition